En-13
CAUTION
Tighten the indoor unit connection cable and power supply indoor and outdoor unit,
branch box terminal board connections fi rmly with the terminal board screws. Faulty
connection may cause a fi re.
If the indoor unit connection cable and power supply are wired incorrectly, the air
conditioner may be damaged.
Connect the indoor unit connection cable by matching the numbers of the outdoor,
branch box and indoor units terminal board numbers as shown in terminal label.
Earth (Ground) both the indoor and outdoor, branch box units by attaching an earth (a
ground) cable.
Unit shall be earthed (grounded) in compliance with the applicable local and national
cables.
CAUTION
Be sure to refer to the above diagram for do correct fi eld wiring. Wrong wiring causes
malfunction of the unit.
Check local electrical rules and also any specifi c wiring instructions or limitation.
6.2. Connection cable preparation
Keep the earth (ground) wire longer than the other wires.
Power supply cable
or connection cable
20 mm
30mm or more
Earth (Ground) wire
• Use a 4-core wire cable.
6.3. Connection of wiring
(1) Remove the control box cover from the control box.
Screw
Cover
(2) Cable connection
• Connect the connection cable to the terminal board.
• Connect the remote controller cable to the terminal board.
• Fix the remote controller cable to the control box cover with a nylon clamp.
Remote controller cable
1: Red
2: White
3: Black
Cable-tie (Medium)
(Accessories)
Power supply cable
Earth (Ground)
Cable-tie (Medium)
(Accessories)
Remote controller cable
Power supply cable
.
7. REMOTE CONTROLLER SETTING
CAUTION
When detecting the room temperature using the remote con-
troller, please set up the remote controller according to the
following conditions. If the remote controller is not located prop-
erly, the correct room temperature will not be detected, and
thus abnormal conditions like “not cooled” or “not heated” will
occur even if the air-conditioner is running normally.
• Locate where an average temperature for the room being
air conditioned will be sensed.
• Do not locate directly exposed to the outlet air from the
air-conditioner.
• Locate out of direct sunlight.
• Locate away from the infl uence of other heat sources.
Do not touch the remote controller PC board and PC board parts directly with your hands
.
Do not wire the remote controller cable together with or parallel to the connection
cables, and power supply cable of the INDOOR UNIT and OUTDOOR UNIT, BRANCH
BOX. It may cause erroneous operation.
When installing the bus wire near a source of electromagnetic waves, use shielded wire
.
Do not set the DIP switches, either on the air conditioner or the remote controller, in any
way other than indicated in this manual that is supplied with the air conditioner. Doing
so may result in improper operation.
7.1. Installing the remote controller
Open the operation panel on the front of the remote controller, remove the 2 screws indi-
cated in the following fi gure, and then remove the front case of the remote controller.
When installing the remote controller, remove the connector from the front case. The
wires may break if the connector is not removed and the front case hangs down.
When installing the front case, connect the connector to the front case.
Screws
SET BACK
Front case
(back side)
Rear case
Connector
When remote controller cable is concealed
(1) Conceal the remote controller cable.
(2) Pass the remote controller cable through the hole in the rear case and connect the
remote controller cable to the remote controller terminal board specifi ed in fi gure.
(3) Clamp the remote controller cable sheath with the cable-tie as shown in fi gure.
(4) Cut off the excess cable-tie.
(5) Install the rear case to the wall, box, etc., with 2 screws fi gure.
Cable-tie
(Small)
1. Red
2. White
3. Black
CAUTION
When connecting the remote controller
wires, do not overtighten the screws.
Hole
Temperature
sensor