EasyManuals Logo

Fujitsu ASU24RLF Service Instruction

Fujitsu ASU24RLF
105 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
01-28
3 sec later Compressor : OFF
3 sec later Outdoor fan motor : OFF
28sec later 4WAY valve : OFF
34sec later Compressor : ON
(Not defrosted for 6 or 10 minutes)
Heating operation start : Compressor ON
Outdoor HEX temp.: Over 53.3°F(12°C)
or
Compressor ON time: Maximum 15 minutes
Defrost end
Integrating defrost
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Defrost start
Normal defrost
Compressor
integrating
operation:
Over 210 min.
When the
compressor is
stopped, If detected
outside air temp.
at 35.6°F(2°C)
Intermittent operation
Compressor
OFF count :
40 times
(Less than 10min.)
Continuous operation
Outdoor HEX
temp.Below
14.0°F (-10°C)
Outside air temp.
> 30.2°F(-1°C)
Outdoor HEX
temp.Below
10.3°F (-12°C)
Outside air temp.
< 30.2°F(-1°C)
For AOU36RLXFZ
=

Other manuals for Fujitsu ASU24RLF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASU24RLF and is the answer not in the manual?

Fujitsu ASU24RLF Specifications

General IconGeneral
BrandFujitsu
ModelASU24RLF
CategoryAir Conditioner
LanguageEnglish

Related product manuals