Trouble shooting 5
OUTDOOR UNIT Error Method:
Indicate or Display:
Outdoor Unit : LED 0.1sec ON/ 0.1sec OFF
Indoor Unit : Operation LED : 3 times, Timer LED : 3 times
ERROR CODE : [E : 06]
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
4.775.987.569.6312.416.121.027.8Resistance Value (k )
23
°F
(-5°C)
14°F
(-10°C)
Temperature
OKOK
OKOK
DC
3.84
0.446
194
°F
(90°C)
0.606
176
°F
(80°C)
0.8401.191.712.082.533.11Resistance Value (k )
158
°F
(70°C)
140°F
(60°C)
Temperature
0.333
212
°F
(100°C)
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
CN62 CN61
3 2 1 4 3 2 1
BLACK
BLACK
Outdoor Heat Exchanger Temperature
Sensor (Outlet) Error
Outdoor Unit Main PCB Circuit
Heat Exchanger Temperature Thermistor
When Heat Exchanger Temperature Thermistor (Outlet) open or
short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
06-09
3 2 1 4 3 2 1
95°F
(35°C)
86°F
(
30°C)
77°F
(
25°C)
68°F
(20°C)
59°F
(15°C)
50°F
(10°C)
41°F
(5°C)
32°F
(0°C)
122°F
(
50°C)
113°F
(45°C)
104°F
(
40°C)