TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring
1. Operate on Colling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
ASU9RL
ASU12RL
ASU9RL
ASU12RL
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
Measure the low pressure with the pressure meter at the service valve.
Measure the outdoor unit overall current with the current clamp meter at Power Cable.
Low-pressure of outdoor unit [MPa]
Outdoor total electric current [A]
07-04
[60Hz-230V]
0.7
0.8
0.9
1.0
1.1
1.2
1.3
In/outdoor ambient temparature [degF (degC)]
60.8
(16)
64.4
(18)
68
(20)
71.6
(22)
75.2
(24)
78.8
(26)
82.4
(28)
86
(30)
89.6
(32)
RH50%
RH60%
RH70%
[60Hz-230V]
2.6
2.8
3.0
3.2
3.4
3.6
RH50%
RH60%
RH70%
7-2. Outdoor unit Pressure Value and Total Electric Current Curve
7-2-1 Cooling operation
In/outdoor ambient temparature [degF (degC)]
60.8
(16)
64.4
(18)
68
(20)
71.6
(22)
75.2
(24)
78.8
(26)
82.4
(28)
86
(30)
89.6
(32)
Low-pressure of outdoor unit [MPa]
[60Hz-230V]
0.7
0.8
0.9
1.0
1.1
1.2
1.3
In/outdoor ambient temparature [degF (degC)]
60.8
(16)
64.4
(18)
68
(20)
71.6
(22)
75.2
(24)
78.8
(26)
82.4
(28)
86
(30)
89.6
(32)
RH50%
RH60%
RH70%
Outdoor total electric current [A]
[60Hz-230V]
2.6
2.8
3.0
3.2
3.4
3.6
RH50%
RH60%
RH70%
In/outdoor ambient temparature [degF (degC)]
60.8
(16)
64.4
(18)
68
(20)
71.6
(22)
75.2
(24)
78.8
(26)
82.4
(28)
86
(30)
89.6
(32)