11) Control switching of external heaters
Sets the control method for external heater to be used.
For details, refer to “External heater output” in Chapter 2-4. "Details of function" on page 05-15.
Function
number
Setting value Setting description
Factory
setting
61
00 Auxiliary heater control 1
01 Auxiliary heater control 2
02 Heat pump prohibition control
03 Auxiliary heater control by outdoor temperature 1
04 Auxiliary heater control by outdoor temperature 2
12) Operating temperature switching of external heaters
Sets the temperature conditions when the external heater is ON.
For details, refer to “External heater output” in Chapter 2-4. "Details of function" on page 05-15.
Function
number
Setting value
Setting description
Factory
setting
Heater: On Heater: Off
62
00 -5.4 °F (-3 °C) -1.8 °F (-1 °C)
01 -3.6 °F (-2 °C) -1.8 °F (-1 °C)
02 -3.6 °F (-2 °C) -1.8 °F (-1 °C)
03 -5.4 °F (-3 °C) -1.8 °F (-1 °C)
04 -7.2 °F (-4 °C) -1.8 °F (-1 °C)
05 -9.0 °F (-5 °C) -1.8 °F (-1 °C)
13) Outdoor temperature zone boundary temperature A
Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is re-
quired when auxiliary heater control by outdoor temperature 1 and 2 are performed on the indoor
unit. For details, refer to “External heater output” in Chapter 2-4. "Details of function" on page 05-
15.
Function number Setting value Setting description Factory setting
66
00 -4.0 °F (-20 °C)
01 -0.4 °F (-18 °C)
02 3.2 °F (-16 °C)
03 6.8 °F (-14 °C)
04 10.4 °F (-12 °C)
05 14.0°F (-10 °C)
06 17.6 °F (-8 °C)
07 21.2 °F (-6 °C)
08 24.8 °F (-4 °C)
1-1. Function settings by using remote controller - (05-7) - 1. Function settings
FIELD
WORKING
FIELD
WORKING