Available Sensor ID
Sensor ID Item Unit Remarks
00 158
Cooling thermostat On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 159
Requested cooling strength On/Off
(External output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 160
External heater On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 161
Heating operation status (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 162
External output command by remote
controller (External output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
01: Outdoor unit
01 000 Outdoor temp. 01: °F or °C
01 001 Discharge temp. 01: °F or °C
01 004 Heat exchanger outlet temp. 01: °F or °C
01 050 Fan 1 rotation number 03: rpm
01 055 Compressor rotation number 04: rps
01 060
Expansion valve (Upstream during
heating)
05: pls
01 080 4-way valve output status
07: Cooling/
Heating
0: Cooling, 1: Heating
01 089 Base heater output On/Off 08: On/Off 0: Off, 1: On
01 100 Operating current 09: A
01 110 Outdoor unit total power-on hours 11: h
01 111
Compressor total heating operation
hours
11: h
01 112
Compressor total cooling operation
hours
11: h
01 113 Compressor total operation hours 11: h
01 114
Outdoor unit fan 1 total operation
hours
11: h