EasyManuals Logo

Fujitsu ASUH24LPAS Service Manual

Fujitsu ASUH24LPAS
169 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #146 background imageLoading...
Page #146 background image
2-3. Combination of external input and output
By combining the function setting of the indoor unit and rotary switch setting of the External Input
and Output PCB, you can select various combinations of functions.
Combination examples of external input and output are as follows:
Mode
Function
setting
Rotary
SW
External input
Indoor unit External Input and Output PCB
CN46
1
CN313
2
CN314
0-1 60—00 1
Operation/Stop
(Function setting 46-00)
or
Forced stop
(Function setting 46-02)
Operation/Stop Not available
Operation Stop
0-2 60-00 2 Forced thermostat Off
Not available
1 60-01 3
Mechanical cooling
Off
2 60-02 4 Forced thermostat Off
3 60-03 5
Mechanical cooling
On
4 60-04 6
Mechanical cooling
On
5 60-05 7 Forced thermostat Off
6 60-06 8 Forced thermostat Off
7 60-07 9
Mechanical cooling
Off
8 60-08 A Forced thermostat Off
9 60-09 B Forced thermostat Off
10 60-10 C Forced thermostat Off
11 60-11 D Forced thermostat Off
Mode
Function
setting
Rotary
SW
External output
Indoor unit External Input and Output PCB
CN47
1
CN310
2
CN311
3
CN312
0-1 60-00 1 Operation/Stop Operation/Stop Error status
Indoor unit fan
operation status
0-2 60-00 2 Operation/Stop Error status
Indoor unit fan
operation status
External heater
output
1 60-01 3
Cooling
thermostat On
Error status
Indoor unit fan
operation status
External heater
output
2 60-02 4
Cooling
thermostat On
Error status
Remote
controller output
External heater
output
3 60-03 5
Cooling
thermostat On
Cooling high/low
output
Remote
controller output
External heater
output
4 60-04 6
Cooling
thermostat On
Error status
Remote
controller output
Cooling high/low
output
5 60-05 7
Heating
thermostat On
Error status
Indoor unit fan
operation status
External heater
output
6 60-06 8 Operation/Stop Error status
Indoor unit fan
operation status
Heating
thermostat On
7 60-07 9
Cooling
thermostat On
Error status
Heating
thermostat On
External heater
output
8 60-08 A
Cooling
thermostat On
Heating
thermostat On
Remote
controller output
External heater
output
9 60-09 B Error status Operation/Stop
Indoor unit fan
operation status
External heater
output
10 60-10 C
Indoor unit fan
operation status
Operation/Stop Error status
External heater
output
2-3. Combination of external input and output - (05-16) - 2. External input and output
FIELD
WORKING
FIELD
WORKING

Table of Contents

Other manuals for Fujitsu ASUH24LPAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASUH24LPAS and is the answer not in the manual?

Fujitsu ASUH24LPAS Specifications

General IconGeneral
BrandFujitsu
ModelASUH24LPAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals