1-3. Error code table (Indoor unit and wired remote controller)
The operation, timer, and economy indicators operate according to the error contents.
For confirmation of the error contents, refer the flashing pattern as follows.
Error contents
Indoor unit display Wired
remote
controller
display
Operation [ ]
(Green)
Timer [ ]
(Orange)
Economy [ ]
(Green)
E: 11. Serial communication error (Serial
reverse transfer error) (Outdoor unit)
1 times 1 times Continuous 11
E: 11. Serial communication error (Serial
forward transfer error) (Indoor unit)
1 times 1 times Continuous 11
E: 12. Wired remote controller
communication error (Indoor unit)
1 times 2 times Continuous 12
E: 18. External communication error (Indoor
unit)
1 times 8 times Continuous 18
E: 32. Indoor unit main PCB error (Indoor
unit)
3 times 2 times Continuous 32
E: 35. MANUAL AUTO button error (Indoor
unit)
3 times 5 times Continuous 35
E: 41. Room temperature sensor error
(Indoor unit)
4 times 1 times Continuous 41
E: 42. Indoor unit heat exchanger sensor
error (Indoor unit)
4 times 2 times Continuous 42
E: 51. Indoor unit fan motor error (Indoor
unit)
5 times 1 times Continuous 51
E: 58. Intake grille error (Indoor unit) 5 times 8 times Continuous 58
E: 62. Outdoor unit main PCB error
(Outdoor unit)
6 times 2 times Continuous 62
E: 63. Inverter error (Outdoor unit) 6 times 3 times Continuous 63
E: 64. PFC circuit error (Outdoor unit) 6 times 4 times Continuous 64
E: 65. IPM error (Outdoor unit) 6 times 5 times Continuous 65
E: 71. Discharge thermistor error (Outdoor
unit)
7 times 1 times Continuous 71
E: 72. Compressor thermistor error
(Outdoor unit)
7 times 2 times Continuous 72
E: 73. Outdoor unit heat exchanger
thermistor error (Outdoor unit)
7 times 3 times Continuous 73
E: 74. Outdoor temperature thermistor error
(Outdoor unit)
7 times 4 times Continuous 74
E: 84. Current sensor error (Outdoor unit) 8 times 4 times Continuous 84
E: 94. Trip detection (Outdoor unit) 9 times 4 times Continuous 94
E: 95. Compressor motor control error
(Outdoor unit)
9 times 5 times Continuous 95
E: 97. Outdoor unit fan motor error
(Outdoor unit)
9 times 7 times Continuous 97
E: 99. 4-way valve error (Outdoor unit) 9 times 9 times Continuous 99
E: A1. Discharge temperature error
(Outdoor unit)
10 times 1 times Continuous A1
E: A3. Compressor temperature error
(Outdoor unit)
10 times 3 times Continuous A3
1-3. Error code table (Indoor unit and wired remote controller) - (03-2) - 1. Error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu ASUH24LPAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASUH24LPAS and is the answer not in the manual?

Fujitsu ASUH24LPAS Specifications

General IconGeneral
BrandFujitsu
ModelASUH24LPAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals