EasyManuals Logo

Fujitsu ASUH24LPAS Service Manual

Fujitsu ASUH24LPAS
169 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #98 background imageLoading...
Page #98 background image
Limit of maximum speed based on outdoor temperature
A zone
B zone
C zone
D zone
E zone
F zone
Outdoor
temperature drops
Outdoor
temperature rises
93.2°F
(34°C)
96.8°F
(36°C)
86.0°F
(30°C)
66.2°F
(19°C)
50.0°F
(10°C)
32.0°F
(0°C)
89.6°F
(32°C)
69.8°F
(21°C)
53.6°F
(12°C)
35.6°F
(2°C)
Unit: rps
Model name
Outdoor
temperature zone
Indoor unit fan mode
HIGH MED LOW QUIET
ASUH18LPAS
A zone 80 46 36 22
B zone 80 46 36 22
C zone 80 46 36 22
D zone 50 39 32 22
E zone 50 39 32 22
F zone 50 39 32 22
ASUH24LPAS
A zone 111 46 36 26
B zone 111 46 36 26
C zone 111 46 36 26
D zone 54 39 32 26
E zone 54 39 32 26
F zone 54 39 32 26
1-1. Cooling operation - (04-2) - 1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Other manuals for Fujitsu ASUH24LPAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASUH24LPAS and is the answer not in the manual?

Fujitsu ASUH24LPAS Specifications

General IconGeneral
BrandFujitsu
ModelASUH24LPAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals