8-2. External output
Use an external output cable with appropriate external dimension, depending on the number of ca-
bles to be installed.
¢
Indoor unit
A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m).
Output voltage: High DC 12 V ± 2 V, Low 0 V.
Permissible current: 50 mA
For details, refer to
"Combination of external input and output" on page 19.
When indicator or other components are connected directly
Example: Function setting 60 is set to "00"
1
2
Connector
(CN47)
LED
PCB
Resistor
Connected unit
+
-
When connecting with a device equipped with a power supply
Example: Function setting 60 is set to "00"
1
2
Connected device
Connector
(CN47)
PCBConnected unit
Relay
(Operation status)
-
+
- 17 -
8-2. External output
8. External input and output
WALL MOUNTED
ASUH30-36LPAS
WALL MOUNTED
ASUH30-36LPAS