Model name ARXH22KMTAP
Power supply 230 V~ 50 Hz
Available voltage range 198—264 V
Capacity kW class 6.0
Input power W 79
Running current A 0.40
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,150
MED 920
LOW 800
QUIET 700
Heating
HIGH 1,150
MED 920
LOW 800
QUIET 700
Type × Qty Sirocco fan × 2
Motor output W 197
Static pressure range Pa 30 to 150
Sound pressure level*
1
Cooling
HIGH
dB (A)
32
MED 28
LOW 25
QUIET 24
Heating
HIGH 32
MED 28
LOW 25
QUIET 24
Sound power level
Cooling
HIGH dB (A)
58
Heating 58
Heat exchanger
Dimensions (H × W × D)
mm
336 × 790 × 39.9
Fin pitch 1.4
Rows × Stages 3 × 16
Pipe type Copper tube
Fin type Aluminum
Enclosure
Material Steel sheet
Color ―
Dimensions
(H × W × D)
Net
mm
240 × 1,000 × 700
Gross 334 × 1,226 × 863
Weight
Net
kg
31
Gross 37
Connection pipe
Size
Liquid
mm (in)
Ø6.35 (Ø1/4)
Gas Ø12.70 (Ø1/2)
Method Flare
Drain port
Material Polyvinyl chloride
Tip diameter mm Ø26 (I.D.), Ø32 (O.D.)
Drain hose
Material Polyvinyl chloride
Tip diameter mm Ø25 (I.D.), Ø32 (O.D.)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Remote controller (Option)
Wireless, Wired, Mobile app*
2
[FGLair
â„¢
, AIRSTAGE Mobile]
NOTES:
• Values mentioned in the table are based on the following conditions:
– Static pressure: 40 Pa
• The protective function might work when using it outside the operation range.
• *
1
: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *
2
: Available on Google Play
â„¢
store or on App Store
®
. Optional WLAN Adapter is also required. For details, refer to the setting manual.
• This data is based on EN 14511 standard.
- 18 -
2-4. Medium static pressure duct type
2. Specifications
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE