1-2. Outdoor units
Type Inverter heat pump
Model name AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Starting current A 2.8 3.5 4.8 6.4
Fan
Airflow rate
Cooling
m
3
/h
1,610 1,680
Heating 1,560 1,610 1,580
Type × Q'ty Propeller fan × 1
Motor output → 23
Sound pressure level *1
Cooling
dB (A)
46 50
Heating 46 48 50
Sound power level
Cooling
dB (A)
61 65
Heating 62 63 66
Heat exchanger type
Dimensions
(H × → × D)
mm
Main1: 504 × 888 × 18.19
Main2: 504 × 510 × 18.19
Main1: 504 × 881 × 18.19
Main2: 504 × 801 × 18.19
Fin pitch 1.3
Rows × Stages 1.5 × 24 2 × 24
Pipe type Copper
Fin type
Type (Material) Aluminum
Surface treatment PC Fin
Compressor
Type DC Rotary
Motor output → 900
Refrigerant
Type (Global warming potential) R32 (675)
Charge g 750 850
Refrigerant oil
Type RB68A
Amount
cm
3
340
Enclosure
Material Steel sheet
Color
Beige
Approximate color of Munsell 10↔R 7.5/1.0
Dimensions
(H × → × D)
Net
mm
542 × 799 × 290
Gross 602 × 940 × 375
→eight
Net
kg
30 31 32
Gross 34 35 36
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas Ø 9.52 (Ø 3/8)
Method Flare
Pre-charge length
m
15
Max. length 20
Max. height difference 15
Operation range
Cooling
°C
-10 to 46
Heating -15 to 24
Drain hose
Material PP
Size mm Ø 13.0 (I. D.), Ø 16.0 to Ø 16.8 (O. D.)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °C→B, and outdoor temperature of 35 °CDB/24 °C→B.
– Heating: Indoor temperature of 20 °CDB/15 °C→B, and outdoor temperature of 7 °CDB/6 °C→B.
– Pipe length: 5 m, Height difference: 0 m.
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
1-2. Outdoor units - (01-3) - 1. Specifications