( Fig.1 : Outdoor temperature zone )
1. COOLING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
Minimum
frequency
Maximum
frequency
07/09
12
18rps
16rps
64rps
87rps
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Indoor fan mode
Me Lo Quiet
A zone 64rps 51rps 42rps 30rps
B zone 64rps 51rps 42rps 30rps
C zone 64rps 51rps 42rps 30rps
Model
07, 09
D zone 48rps 45rps 39rps 30rps
E zone 48rps 45rps 39rps 30rps
F zone 48rps 45rps 39rps 30rps
( Table 1 : Compressor frequency range )
01-01
E zone
F zone
10°C
0°C
12°C
2°C
* When the room temperature is between +2°C to -2.5°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Fig.1 based on the indoor
fan mode and the outdoor temperature.
* If the room temperature is some degrees lower than a set temperature,
the compressor will be stopped.
12
A zone 87rps 55rps 46rps 30rps
B zone 87rps 55rps 46rps 30rps
C zone 87rps 55rps 46rps 30rps
D zone 62rps 52rps 44rps 30rps
E zone 62rps 52rps 44rps 30rps
F zone 62rps 52rps 44rps 30rps
When the outdoor
temperature drops
When the outdoor
temperature rises
( Table 2 : Limit of maximum speed based on outdoor temperature )
Outdoor
temp. zone
Hi
* If the room temperature is 2°C higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
Model