6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
6-1. Models: AOYG07KGCA, AOYG09KGCA, AOYG12KGCA,
and AOYG14KGCA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.858 0.868
10 0.929 0.872 0.882
7.5 0.960 0.933 0.876 0.885
5 0.992 0.964 0.937 0.879 0.889
0 1.000 0.972 0.944 0.887 0.896
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.972 0.944 0.887 0.896
-7.5 0.972 0.944 0.887 0.896
-10 0.944 0.887 0.896
-15 0.887 0.896
HEATING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.896 0.879
10 0.968 0.890 0.879
7.5 0.994 0.968 0.896 0.879
5 1.000 0.994 0.968 0.896 0.879
0 1.000 0.994 0.968 0.896 0.879
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.989 0.963 0.891 0.875
-7.5 0.987 0.961 0.889 0.873
-10 0.959 0.887 0.871
-15 0.878 0.862
- 51 -