EasyManua.ls Logo

Fujitsu ASYG14KETA - Page 40

Fujitsu ASYG14KETA
125 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Grating
PROHIBITED
WARNING
The appliance shall be installed, operated and stored in a room with a floor area larger than X
m
2
.
Amount of refrigerant charge
M (kg)
Minimum room area
X (m
2
)
M ≤ 1.22 -
1.22 < M ≤ 1.23 12.99
1.23 < M ≤ 1.50 19.31
1.50 < M ≤ 1.75 26.28
1.75 < M ≤ 2.0 34.33
2.0 < M ≤ 2.5 53.63
2.5 < M ≤ 3.0 77.23
3.0 < M ≤ 3.5 105.12
3.5 < M ≤ 4.0 137.29
(IEC 60335-2-40)
2-6. Floor type - (01-34) - 2. Dimensions
GENERAL
INFORMATION
GENERAL
INFORMATION

Other manuals for Fujitsu ASYG14KETA

Related product manuals