05-23
Thermistor resistance value <Outdoor unit side>
Temperature
[°C]
Resistance Value [ k ]
Thermistor A Thermistor B Thermistor C
- 20
- 10
- 5
0
5
10
15
20
25
30
40
50
60
70
80
90
100
110
120
---
---
---
168.6
129.8
100.9
79.1
62.6
49.8
40.0
26.3
17.8
12.3
8.7
6.3
4.6
3.4
2.6
2.0
---
27.8
21.0
16.1
12.4
9.6
7.6
6.0
4.8
3.8
2.5
1.7
1.2
---
---
---
---
---
---
105.4
58.2
44.0
33.6
25.9
20.2
15.8
12.5
10.0
8.0
5.3
3.6
--
-
---
---
---
---
---
---
Applicable
Thermistors
Discharge temp. TH1
Comp.1 temp. TH10
Outdoor temp. TH3Heat exchanger. TH5
Suction temp. TH4
Sub-cool heat exchanger
Gas (inlet) TH8
Sub-cool heat exchanger
Gas (outlet) TH9
Sub-cool heat exchanger
Liquid temp TH7
6.5
35
8.0
30
10.012.515.820.125.233.6Resistance Value ( )
2520151050
Temperature (°C)
3.54.35.3Resistance Value ( )
504540
Temperature (°C)
Indoor Temperature Thermistor (TH21)
Resistance Value ( )
Temperature (°C)
32.4
35
40.0
30
49.862.579.1100.9129.8168.6
2520151050
Resistance Value ( )
Temperature (°C)
17.821.226.3
504540
Heat Exchanger Thermistor (Inlet TH22 / Outlet TH23)
Thermistor resistance value <Indoor unit side>
5-3-2 Thermistor resistance