Error Contents :
Communication Error
with Group Remote Controller
Symptom :
Error Code display [ 1 2 ] Control/Display from Group Remote is
not available.
Details :
Condition of occurrence : The communication between Group Remote and Network Convertor was not normally performed.
Release condition : When the communication between Group Remote and Network Convertor resumes normal operation.
Cause 2 :
Defective or open connection of cable wire between Network Convertor and Connected Remote Controller.
After the following are checked, the power supply is reset.
Check connection cable wire between Network Convertor and Connected Remote Controller.
Check connection between Control PCB and Terminal.
Cause 3 : Incorrect setting of Network Convertor's DIP-SW103[1 to 4]
Check Network Convertor PCB DIP-SW103[1 to 4] ON.
OK
OK
Cause 4 : Defective Remote Controller or Network Convertor.
Replace Remote Controller or Network Convertor.
Cause 1 : External noise
After pressing SW104 of Network Convertor PCB for 5 seconds or turning on power.
Does error code display reappear?
It is not a defect of PCB. Remove the surrounding noise source.Remove the surrounding noise source.
YES
OK
NO
Trouble shooting 85
Network Convertor (UTY-VGGXZ1) Group Remote controller Setting -
04-93

Table of Contents

Other manuals for Fujitsu AUXB07GALH

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXB07GALH and is the answer not in the manual?

Fujitsu AUXB07GALH Specifications

General IconGeneral
BrandFujitsu
ModelAUXB07GALH
CategoryAir Conditioner
LanguageEnglish

Related product manuals