EasyManua.ls Logo

Fujitsu AUXB14GALH - Sub-cool Heat EX. Gas outlet Temp Sensor Error<TH9> Troubleshooting

Fujitsu AUXB14GALH
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Sub-cool Heat EX. Gas outlet
Temp Sensor Error<TH9>
OK
DC
CN142
BLACK
BLACK
1234
1234
BLACK
BLACK
Sub-cooling heat exchanger gas outlet
temperature thermistor
Sub-cooling heat exchanger gas outlet temperature thermistor short or
open detected
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
OK
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 17".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN142:3-4) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
Sub-cooling heat exchanger gas outlet temperature sensor (CN142:3-4)
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. 82. 2
Error Code : 82
THERMISTOR
(SC.EXT.GAS)
< TH 9 >
THERMISTOR
(SC.EXT.LIQ)
Trouble shooting 47
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
E. 82.2
04-55