EasyManuals Logo

Fujitsu AUXB14GALH User Manual

Fujitsu AUXB14GALH
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
02-05
2-3-2 Heating Operation
Switching conditions of step
Fan step
8HP&10HP: 11 / 12HP: 13
6
0
Outside air temperature
sensor detected value
TAOUT 0°C
0°C TAOUT 5°C
5°C TAOUT
Thereafter, the high-pressure is monitoring at a set time interval and the fan speed is changed by the following conditions.
(Condition which lowers the fan speed)
Low-pressure 0.85MPa and heat sink temperature
(Condition which raises the fan speed)
Low-pressure saturation 0.74MPa or heat sink temperature
The initial speed of the first boot outdoor unit is detected by outdoor air temperature sensor value (TAOUT).
Fan step
11
10
9
8
7
6
5
4
3
2
1
0
680
680
660
660
590
510
520
400
440
330
380
300
300
300
450
0
300
0
0
0
0
0
Fan speed (rpm)
780
740
660
660
590
510
520
400
440
330
380
300
300
300
450
0
300
0
0
0
0
0
790
710
700
620
590
510
520
400
440
330
380
300
300
300
450
0
Intermittent 1
0
0
0
0
0
Step
Upper FAN
Lower FAN
AJ*072LELAH
AJ*090LELAH AJ*108LELAH
13
12
-
-
-
-
-
-
-
-
960
880
870
790
Intermittent 2
300
Intermittent 1
Intermittent 2
Intermittent 1
Intermittent 2
Intermittent 1 : 14 sec. ON (300rpm), 17 sec. OFF
Intermittent 2 : 19 sec. ON (300rpm), 17 sec. OFF
55°C: 8&10HP
60°C: 12HP
60°C: 8&10HP
65°C: 12HP

Table of Contents

Other manuals for Fujitsu AUXB14GALH

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXB14GALH and is the answer not in the manual?

Fujitsu AUXB14GALH Specifications

General IconGeneral
BrandFujitsu
ModelAUXB14GALH
CategoryAir Conditioner
LanguageEnglish

Related product manuals