EasyManua.ls Logo

Fujitsu AUXB14GALH - Indoor Unit Microcomputer Self-Check Error Troubleshooting

Fujitsu AUXB14GALH
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Trouble shooting 16 E32. 7
INDOOR UNIT Error Method:
Indoor unit microcomputer
self-check error
Indicate or Display:
Indoor Unit : Operation LED 3 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 3 2
Detective Actuators:
Indoor Unit Controller PCB Circuit
Detective details:
When the error is detected by the self-diagnosis of a microcomputer
Forecast of Cause :
1. Outside cause 2. Defective connection of electric component 3. Controller PCB defective
Check Point 1-2 :
Check outside cause (Voltage drop or noise, etc.)
Instant drop --- Check if there is a large load electric apparatus
in the same circuit.
Momentary power failure ----- Check if there is a defective
contact or leak current in the
power supply circuit.
Noise ----- Check if there is any equipment causing harmonic
wave near electric line (Neon bulb or electric
equipment that may cause harmonic wave).
Check the complete insulation of grounding.
Check Point 3 : Replace Controller PCB
Change Controller PCB and set up the original address.
Check Point 1-1 : Reset Power Supply
Check Point 2 :
Check Indoor Unit electric components
YES
NO
Does abnormal LED indication show again?
Check all connectors (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
OK