EasyManua.ls Logo

Fujitsu AUXG22KVLA - Page 126

Fujitsu AUXG22KVLA
229 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
¢
Power supply cable wiring
Power cable
Junction box—indoor unit (primary) 3-wires
Junction box—indoor unit (secondary) 2-wires
Outdoor unit 2-wires
Bus wire Indoor unit—indoor unit 3-wires
Remote controller cable 3-wires
Example:
Outdoor unit
Remote controller
Power cable
6.0 mm
2
× 2-wires
Junction box
(Locally purchased)
Power cable
(Junction box - indoor unit
connection cable)
1.5 mm
2
× 3-wires
Power cable
(Junction box - indoor unit
connection cable)
1.5 mm
2
× 2-wires
Remote controller cable
0.33 mm
2
× 3-wires
Bus wire
(Indoor unit - indoor unit
connection cable)
0.33 mm
2
× 3-wires
Main breaker
30 A
Power supply
230 V ~ 50 Hz
Indoor unit
(Secondary)
Indoor unit
(Primary)
- 118 -
4-2. Power supply cable wiring 4. Wiring design
SYSTEM
DESIGN
SYSTEM
DESIGN

Table of Contents

Related product manuals