8-3. Current release control
The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur-
rent limit value set according to the outdoor temperature.
The compressor frequency returns according to the operation mode, when the current becomes low-
er than the release value.
¢ Models: AOYG30KATA and AOYG36KATA
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
52°C ≤ Ta 8.0 A 7.5 A
50°C ≤ Ta < 52°C 12.0 A 11.5 A
42°C ≤ Ta < 50°C 14.0 A 13.5 A
2°C ≤ Ta < 42°C 18.0 A 17.5 A
Ta < 2°C 20.0 A 19.5 A
Heating
2°C ≤ Ta 18.0 A 17.5 A
Ta < 2°C 20.0 A 19.5 A
¢ Model: AOYG45KATA
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
52°C ≤ Ta 10.0 A 9.5 A
50°C ≤ Ta < 52°C 13.0 A 12.5 A
46°C ≤ Ta < 50°C 15.0 A 14.5 A
42°C ≤ Ta < 46°C 18.0 A 17.5 A
2°C ≤ Ta < 42°C 20.0 A 19.5 A
Ta < 2°C 24.0 A 23.5 A
Heating
2°C ≤ Ta 20.0 A 19.5 A
Ta < 2°C 24.0 A 23.5 A
¢ Model: AOYG54KATA
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
52°C ≤ Ta 10.0 A 9.5 A
50°C ≤ Ta < 52°C 13.0 A 12.5 A
46°C ≤ Ta < 50°C 15.0 A 14.5 A
42°C ≤ Ta < 46°C 18.0 A 17.5 A
2°C ≤ Ta < 42°C 20.0 A 19.5 A
Ta < 2°C 24.0 A 23.5 A
Heating
12°C ≤ Ta 20.0 A 19.5 A
2°C ≤ Ta < 12°C 21.0 A 20.5 A
Ta < 2°C 24.0 A 23.5 A
8-3. Current release control - (04-34) - 8. Various protections