SERVICE PARTS INFORMATION 8
Thermistor
02-47
Check Point : Check Thermistor resistance value
Remove connector and check Thermistor resistance value.
Temperature
[°C]
Resistance Value [ k ]
Thermistor A Thermistor B Thermistor C Thermistor D
Applicable
Thermistors
Discharge temp. TH
Compressor temp. TH
Outdoor temp. TH Heatsink temp. THHeat exchanger. TH
-30
-20
-10
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
1013.1
531.6
292.9
168.6
100.9
62.5
40.0
26.3
17.8
12.3
8.7
6.3
4.6
3.4
2.6
2.0
---
---
---
95.6
50.3
27.8
16.1
9.6
6.0
3.8
2.5
1.7
1.2
0.8
0.6
---
---
---
---
---
---
---
224.3
115.2
62.3
35.2
20.7
12.6
8.0
5.2
3.5
2.4
---
---
---
---
---
---
---
---
---
94.3
49.6
27.4
15.8
9.5
5.9
3.8
2.5
1.7
1.2
0.8
0.6
0.4
0.3
0.2
0.2
0.1
0.1
0.1