EasyManua.ls Logo

Fujitsu GENERAL ABHG18KRTA - Model: AOHG30 KATA

Fujitsu GENERAL ABHG18KRTA
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-4. Model: AOHG30KATA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 20 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30 0.926
20 0.953 0.942
10 0.979 0.968 0.958
7.5 0.988 0.983 0.972 0.961
5 0.992 0.992 0.987 0.976 0.965
0 1.000 1.000 0.995 0.984 0.973
Indoor unit is lower
than outdoor unit *2
-5 1.000 1.000 0.995 0.984 0.973
-7.5 1.000 0.995 0.984 0.973
-10 0.995 0.984 0.973
-20 0.984 0.973
-30 0.973
HEATING
Pipe length (m)
5 7.5 10 20 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30 0.931
20 0.954 0.931
10 0.990 0.954 0.931
7.5 1.000 0.990 0.954 0.931
5 1.000 1.000 0.990 0.954 0.931
0 1.000 1.000 0.990 0.954 0.931
Indoor unit is lower
than outdoor unit *2
-5 0.995 0.995 0.986 0.949 0.926
-7.5 0.993 0.983 0.946 0.924
-10 0.981 0.944 0.921
-20 0.935 0.912
-30 0.903
- 85 -
6-4. Model: AOHG30KATA 6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOHG18-45KATA
OUTDOOR UNIT
AOHG18-45KATA

Table of Contents

Related product manuals