7. Additional charge calculation
7-1. Model: AOHG09KMCDN
Refrigerant type R32
Refrigerant amount g 850
Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100
7-2. Model: AOHG12KMCDN
Refrigerant type R32
Refrigerant amount g 940
Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100
7-3. Model: AOHG14KMCDN
Refrigerant type R32
Refrigerant amount g 1,120
Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100
- 55 -
7-1. Model: AOHG09KMCDN 7. Additional charge calculation
OUTDOOR UNIT
AOHG09-14KMCDN
OUTDOOR UNIT
AOHG09-14KMCDN