EasyManua.ls Logo

Fujitsu General ASHG09KMCDN - Safety Devices

Fujitsu General ASHG09KMCDN
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11. Safety devices
Type of protection Protection form
Model
AOHG09KMCDN AOHG12KMCDN AOHG14KMCDN
Circuit protection Current fuse (Main PCB)
250 V, 25 A
250 V, 5 A
Fan motor
protection
Thermal protection
Activate
103±18 °C
Fan motor stop
125±10 °C
Fan motor stop
Reset
95±18 °C
Fan motor restart
120±10 °C
Fan motor restart
Compressor
protection
Terminal protection
program
(Discharge temp.)
Activate
110 °C
Compressor stop
Reset
After 7 minutes
Compressor restart
Thermal protection
program
(Outdoor temp.)
(Only in COOL or DRY
mode)
Activate
-15 °C
Compressor stop
Reset
-10 °C
Compressor restart
- 60 -
11. Safety devices
OUTDOOR UNIT
AOHG09-14KMCDN
OUTDOOR UNIT
AOHG09-14KMCDN

Table of Contents

Related product manuals