Gammaflux GLC 2k - User Manual

Gammaflux GLC 2k
4 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Enter
Change Area
Automatic/
Manual Selectionl
Temperature Set Select
Zone select indication
Temperature holding set point
Low temperature alarm
Select
Zone Select/Status Area
GLC 2K Start Up Procedure
1
Dry Cycle Mold, Apply Full Tonnage, 3-4 Times (Pinch any wires in
advance of operation)
2
Turn Individual Zones “Off
3
Turn “On” Main Disconnect
4
Select Zone or Zones, Press 1st Zone, Hold, Press Last Zone, Hold, Release.
All Zones Lit are Selected
5
Change Area – Select Temperature Set, Enter Set Point, Press Enter, All
Zones Selected will Change
6
Select Zone or Zones, Press 1st Zone, Hold, Press Last Zone, Hold, Release.
All Zones Lit are Selected
7
Change Area – Select Automatic/Manual Selection, Enter “0” for Automatic
Operation, Press Enter
8
Turn “On” Zone Power Switch. Apply Power to Manifolds first if required
by Manifold Supplier
9
Zones will read a Low Temperature Alarm, Zones are close or holding Set
Point When the Green Temperature Holding Set Point Light is Illuminated
Gammaflux
Sterling, VA USA Tel. +1-(703) 471-5050
Wiesbaden, Germany Tel. +49-(0)-611-973430
Ube, Japan Tel. +81-(836) 54-4369
www.gammaflux.com; www.gammaflux.de
GLC 2k
Version 1.3
Advanced Setup/Troubleshooting
Hot Runner Temperature Controller
12 Zone Maximum per Tier
•1 HBE-24 Female Connector for
Power per Tier (Standard)
•1 HBE-24 Male Connector for
Thermocouple per Tier (Standard)
Remote Mount Alarm Relay
External Communications RS232/RS485
Question and Answer IconNeed help?

Do you have a question about the Gammaflux GLC 2k and is the answer not in the manual?

Gammaflux GLC 2k Specifications

General IconGeneral
BrandGammaflux
ModelGLC 2k
CategoryController
LanguageEnglish

Summary

GLC 2 K Start Up Procedure

Perform Dry Cycle and Tonnage Test

Perform dry cycle mold and full tonnage 3-4 times, ensuring no wires are pinched.

Turn Off Individual Zones

Turn off individual temperature zones before proceeding.

Activate Main Disconnect

Turn on the main disconnect to supply power.

Select Zones for Operation

Select specific zones or all zones for operation by pressing the first and last zone buttons.

Set Zone Temperature Setpoints

Set temperature for selected zones and apply to all selected zones.

Set Automatic;Manual Operation Mode

Select automatic or manual operation mode for zones, entering '0' for automatic.

Turn On Zone Power Switches

Turn on zone power switches, applying power to manifolds first if required.

Monitor Zone Status and Alarms

Monitor zone status for low temperature alarms or set point holding.

View Area and Change Area Controls

View Area Display

Displays actual zone value, degree C/F, deviation, and Amps.

Change Area Controls

Controls for temperature setpoint, manual % setpoint, and trim adjustments.

Boost and Standby Functions

Temporarily increase zone temperature or set zones to standby.

Automatic;Manual Selection

Switch between automatic (0) or manual (1) temperature control.

Zone Select;Status Area

Shows zone selection, status, high/low temp alarms, and set points.

Alarm Area Indicators

Displays status for High/Low Temperature, Thermocouple, Open/Shorted Heater, and Fuse.

Accessing and Navigating Advanced Setup

Accessing Advanced Setup Mode

Press both Select buttons simultaneously to enter Advanced Setup Mode.

Navigating Setup Parameters

Use View Area Select to scroll up and Change Area Select to scroll down.

Modifying Setup Values

Use '+' or '-' keys to make changes and 'Enter' to confirm.

Advanced Setup Guide - Level 2 Security

Restore and Save Mold Set Up

Options to restore or save mold set up configurations.

Boost Set Point and Time

Configure boost set points and boost time for temporary temperature changes.

Automatic Set Point Limit

Set the maximum temperature value for automatic operation.

Temperature Deviation Alarm

Configure set points for temperature deviation alarms.

Standby Set Point

Define the set point for standby mode operation.

Control Algorithm Adjustment

Adjust control algorithm settings, including tuning parameters.

T;C Pinch Detection Time

Configure time settings for thermocouple pinch detection.

Slaved Power Up

Enable or disable slaved power-up for zones to reach set point simultaneously.

Degree F or C Selectable

Select temperature units between Fahrenheit and Celsius.

Thermocouple Input Type

Specify thermocouple input type (J or K).

Host Computer Protocol

Select the host computer communication protocol.

Network Port Device Number

Configure the controller's address on the Euromap 17 network.

Host Baud Rate

Set the communication speed for host computer connection.

Security Code Level 1 & 2

Manage security code levels for access and changes.

Zone Finder Function

Activate zone finder to identify T/C inputs and output modules.

LED Test

Perform an LED test for troubleshooting purposes.

Error Status and Codes

View error status and diagnostic codes for troubleshooting.

Software Version Display

Display software version numbers for controller components.

Security Level Indication

Indicate and adjust security levels (Lockout, Operator, Supervisor).

Basic Troubleshooting and Alarm Interpretation

Alarm Area Interpretation

Understand indicators for High/Low Temperature, Thermocouple issues, and Heater problems.

Troubleshooting Thermocouple Issues

Diagnose Thermocouple Open, Reversed, or Pinched conditions.

Troubleshooting Heater Issues

Diagnose Shorted Heater or Open Heater connection problems.

Troubleshooting Open Fuses

Procedure to check and identify open fuses on the output module.

General Troubleshooting Steps

Perform resistance checks on thermocouples and heaters.

Controller Fault Diagnosis

Steps to identify if the fault lies within the controller unit itself.

Component Identification

Locate and identify key controller components like power supply and output modules.