RG66000889-REV.OO 14
Fan Type Min. Max. M.U. Var.
Galletti
Def.
Presence
F7 - Temperature value for min Winter
speed
- Pressure value for min Winter speed
U F8
F8
F8
50
122
/5
°C
°F
bar
0.1
0.1
0
0
-V-S-
F8 - Temperature value for max Winter
speed
- Pressure value for max Winter speed
U 0
32
/4
F7
F7
F7
°C
°F
bar
0.1
0.1
0
0
-V-S-
F9 - Temp. to turn OFF the fan in Summer
- Pressure to turn OFF the fan in
Summer
U 0
32
/4
F5
F5
F5
°C
°F
bar
0.1
0.1
0
0
-V-S-
FA - Temp. to turn OFF the fan in Winter
- Pressure to turn OFF the fan in Winter
U F7
F7
F7
50
122
/5
°C
°F
bar
0.1
0.1
0
0
-V-S-
Fb Starting time of fans U 0 15 4 sec 1 0 -V-S-
Regulator Type Min. Max M.U. Variation
Galletti
Default
Presence
d1 Defrosting cycle /Condensation
antifreeze
0=no 1=yes
U 0 1 flag 1 0 ---S-
d2 Time-or temperature-based
defrosting0=time1=temperature
U 0 1 flag 1 0 D--S-
d3 - Start defrosting temperature
- Condensation antifreeze alarm set
point
- Start defrosting pressure
U -30
-22
/4
d4
d4
d4
°C
°F
bar
0.1
0.1
0
0
D--S-
d4 - End-defrosting temperature
- End-defrosting pressure
U d3
d3
d3
50
122
/5
°C
°F
bar
0.1
0.1
0
0
D--S-
d5 Min. time-interval to start a defrosting
cycle
U 10 150 sec 10 0 D--S-
d6 Min. duration of a defrosting cycle U 0 150 sec 10 0 D--S-
d7 Max. duration of a defrosting cycle U 1 15 min 1 0 D--S-
d8 Time-delay between 2 defrosting
cycles within the same circuit
U 10 150 min 10 0 D--S-
d9 Defrosting time-interval between the
2 circuits
U 0 150 min 10 0 D--SB
dA Defrost end by external contact F 0 1 flag 1 0 D--S-
db Antifreeze heaters activated while
defrosting
U 0 1 flag 1 0 D--S-
dc Delay before defrosting F 0 3 min 1 0 D--S-
dd Delay after defrosting F 0 3 min 1 0 D--S-
dE End defrosting with 2 refrigerating
circuits and 1 removal fan
F 0 1 flag 1 0 D--SB
Antifreeze Type Min. Max M.U. Variation
Galletti
Def.
Presence
A1 Antifreeze U -30
-22
A4
A4
°C
°F
0.1 4.0 -----
A2 Differential for antifreeze U 0.1
0.1
11.0
19.8
°C
°F
0.1 2.0 -----
A3 Bypass time for antifreeze alarm U 0 150 sec 10 10 -----
A4 Set point for the activation of antifreeze
heater
U A1 rd °C/°F 0.1 0 -----
A5 Diff. for antifreeze heater U 0.1 11.0 °C 0.1 0 -----