Jumper settings and wiring diagrams
C.2 FireShield Technical Reference Manual
Keep power-limited wiring in the shaded
area and nonpower-limited wiring in the
unshaded area at all times.
NOTES
1 All wiring is power-limited except for AC power and battery wiring. All wiring
is supervised unless noted otherwise.
[2] Class A wiring not supported
[3] Listed EOLRs must be installed as shown for proper supervision
[4] For UL installations use EOLR P/N EOL3.6-1.1 which includes one 1.1 k
(P/N EOL1.1) and one 3.6 k (P/N EOL3.6) resistor. For ULC installations
use EOL-P1 and select the 1.1 k and 3.6 k resistors.
ΩΩ
[5] Marking indicates output signal polarity when the circuit is active. Polarity
reverses when the circuit is not active. Wire notification appliances
accordingly. Notification appliance polarity shown in active state.
1.1 k
3.6 k
IDC1–
IDC1+
SS SSWFWF
REMOTE MODULE AND
REMOTE RELAY WIRING
[6]
POWER
ALARM
SUP
TBL
GND FLT
SILEN CE
LMPTST
C–
C+
24VDC+
24VDC–
REMOTE
RELAY
MODULE
(RRM)
WATERFLOW / SUPERVISORY COMBINATION CIRCUIT
[4] [8]
[6] Requires continuous 24 Vdc from the AUX Power
terminals or a power-limited UL/ULC listed compatible
fire signaling power supply
[7] IDC circuits do not support alarm verification using four-
wire smokes. Requires resettable 24 Vdc from AUX
Power terminals.
[8] Combination circuits consist of waterflow switches (WF)
and their associated valve tampers (SS).
[10] Relay circuits can only be connected to power-limited
sources
[11] Installation limits under jurisdiction of local authority
[12] Refer to the
(P/N 3100353) for the topic "Installing the FSDACT."
[9] Automatic and manually activated alarm initiating
devices can be installed on the same IDC circuit
regardless of circuit type except for combination circuits
(option 6, setting 5 and 6)
FireShield Technical Reference Manual
TYPICAL FOUR-WIRE
SMOKE DETECTOR CIRCUIT
[2] [3] [7]
4.7 k
UL/ULC LISTED
EOL RELAY
(shown energized)
IDC1+
24VDC–
24VDC+
IDC1–

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security FireShield FS302 and is the answer not in the manual?

GE Security FireShield FS302 Specifications

General IconGeneral
BrandGE Security
ModelFireShield FS302
CategorySmoke Alarm
LanguageEnglish

Related product manuals