Programming   
3.12    FireShield Technical Reference Manual 
6.  When you press Reset at the last digit (20th digit), the 
system automatically advances you to the next program 
option. 
15. Enter the (DACR2) secondary phone number 
Description: Specifies the secondary phone number that is 
used to contact the central monitoring station. 
Format: Up to 20 digits 
Default: Blank 
To enter the secondary phone number, follow the same steps 
you used to enter the primary phone number. (See “Enter the 
(DACR2) primary phone number” above.) 
16. Enter the (DACR2) account code 
Description: Sets the account code for DACR2. This is the 
code that is used by the monitoring facilities receiver to 
identify the panel location and response information. 
Format: 4 digits 
Default: FFFF 
To enter the account code: 
1.  Press Reset until the first digit of the account code is 
displayed. 
2.  Press Panel Silence to save and advance to the next digit. 
  The trouble buzzer sounds a long beep as confirmation. 
3.  Press Reset until the next digit is displayed. 
4.  Press Panel Silence to save and advance to the next digit. 
5.  Repeat steps 3 and 4 until all digits are entered. 
6.  When you press Reset at the last digit, the system 
automatically advances you to the next program option. 
17. Select the DACR2 alarm format 
Description: Specifies the type of alarm protocol the DACR 
will accept. 
Settings: Contact  ID 
  EST 4/2 (SIA DC-02 P3 with hexadecimal event codes) 
Default: Contact ID 
To select the DACR2 alarm format: 
1.  Press Reset to select the desired format. 
2.  Press Panel Silence to save and advance to the next step. 
  The trouble buzzer sounds a long beep as confirmation. 
18. Select the restore option 
Description: Determines whether or not restoration events are 
sent to the second central monitoring station. 
Settings: Send  restores 
 No restores 
Default: Send restores 
To select the restore option: 
1.  Press Reset to select the restore option for CMS two. 
2.  Press Panel Silence to save. 
  The trouble buzzer sounds a long beep as confirmation. 
19. Enter retry count two 
Description: Sets the maximum number of failed attempts to 
deliver an alarm to a DACR. 
Settings: 5 – 10 retries 
Default: 5 (retries) 
To enter retry count two: 
1.  Press Reset to change the retry count. 
2.  Press Panel Silence to save and advance to the next 
program option. 
  The trouble buzzer sounds a long beep as confirmation. 
20. Enter retry time two 
Description: Sets the delay time before trying to resend an 
alarm to a DACR. 
Format: 2 digits max (5 – 10 seconds) 
Default: 5 (seconds) 
To enter retry time two: 
1.  Press Reset to change the retry time. 
2.  Press Panel Silence to save and advance to the next 
program option. 
  The trouble buzzer sounds a long beep as confirmation. 
21. Select tone or pulse dialing 
Description: Specifies whether the phone line is set up for tone 
dialing or pulse dialing. 
Settings: Tone 
 Pulse 
Default: Pulse 
Note: Touch tone is recommended where available. 
To select tone or pulse dialing: 
1.  Press Reset to select tone or pulse dialing for line 1. 
2.  Press Panel Silence to save. 
  The trouble buzzer sounds a long beep as confirmation.