XXIV. ANSI / SIA CP-01 REQUIREMENTS
To meet SIA CP-01 requirements –
Minimum System Requirements: 1 control panel; 2 keypads (or 1 keypad per partition for multi-partitioned systems)
Remote arming shall NOT be enabled in SIA classified installations.
Off-premise transmission must be in the SIA format.
The Abort window and Entry Delay must not exceed 1 minute.
CAUTION – A call waiting cancel on a non-call waiting line will prevent successful connection to the central station.
CP-01 Feature
Description
Feature Description
as shown in manual
Program
Loc
Seg / Opt
Factory
Default
CP-01 Required
Setting
Exit Time Exit 1 Delay
24
2
60
45 – 240 sec.
Exit 2 Delay
24
4
60
45 – 240 sec.
Progress Annuncation / Disable
– for Silent Exit
Silent Keypad Option
9 3
2
All annunciators enabled Allowed
(individual keypads may be disabled)
Exit Time Restart This feature is non-programmable in the panel. Enabled
Auto Stay Arm on Unvacated Premises Auto Bypass
23
1 / 3
Enabled Enabled
Exit Time and Progress
Annunciation / Disable
– for Remote Arm
This feature is non-programmable in the panel. -- Exit time and progress are always enabled. Enabled (may be disabled for remote arming)
Entry Delay(s) Entry 1 Delay
24
1
30 30 – 240 sec.
Entry 2 Delay
24
3
30 30 – 240 sec.
Abort Window
– for Non-Fire Zones
Dialer Delay
40
8
30 Enabled
(may be disabled by zone/ zone type)
Abort Window Time
– for Non-Fire Zones
Dialer Delay
40
8
30 15 – 45 sec.
NOTE:
Combined
Abort window
and Entry
Delay must
not exceed 1
minute.
Abort Annunciation This feature is non-programmable in the panel. -- Flashing Cancel LED goes off when disarming. Enabled
Cancel Annunciation Cancel
23
3 / 6
Enabled Enabled
Duress Feature Duress
44
Disabled
Disabled
Cross Zoning
2 Trips on Cross Zone
37
5 / 4
Disabled
Required
Keypad sounds on Cross Zone trip
39
5
Disabled
Zone Type Characteristic
111
3 / 4
Disabled
Programmable Cross Zoning Time
Cross Zone Time
40
6
5 minutes
Allowed
Swinger Shutdown Swinger Shutdown Count
38
n/a
Enabled for 1 trip For all non-fire zones, shut down at 1–2 trips
Swinger Shutdown Disable Swinger Shutdown Count
38
n/a
Enabled for 1 trip Allowed
Fire Alarm Verification Fire Alarm Verification Time
40
9
Disabled Required (depends on panel & sensors)
Call Waiting Cancel Must be programmed as part of the
phone number
0
n/a
n/a Required (depends on user phone line)
Default Changes (from prior versions):
Recent Closing
23
3 / 7
Enabled
Exit Error
23
3 / 8
Enabled
Power Up Delay
40
3
60 sec.
IMPORTANT NOTE:
UL requirements take
priority over SIA
requirements.