EasyManua.ls Logo

GE 845 - Page 215

GE 845
552 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 4: SETPOINTS SYSTEM
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–87
Differential and Restraint Current Calculations
Two Winding Transformer
Differential currents are calculated as follows:
Id
A
= I
A
C
[w1] + I
A
C
[w2]
Id
B
= I
B
C
[w1] + I
B
C
[w2]
Id
C
= I
C
C
[w1] + I
C
C
[w2]
Restraint currents are calculated as follows:
Ir
A
= max {|I
A
C
[w1]| , |I
A
C
[w2]|}
Ir
B
= max {|I
B
C
[w1]| , |I
B
C
[w2]|}
Ir
C
= max {|I
C
C
[w1]| , |I
C
C
[w2]|}
where Id
A
, Id
B
and Id
C
are the phase differential currents, and Ir
A
, Ir
B
, and Ir
C
are the phase
restraint currents.
Three-Winding Transformer
Differential currents are calculated as follows:
Id
A
= I
A
C
[w1] + I
A
C
[w2] + I
A
C
[w3]
Id
B
= I
B
C
[w1] + I
B
C
[w2] + I
B
C
[w3]
Id
C
= I
C
C
[w1] + I
C
C
[w2] + I
C
C
[w3]
Restraint currents are calculated as follows:
Ir
A
= max {|I
A
C
[w1]| , |I
A
C
[w2]| , |I
A
C
[w3]|}
Ir
B
= max {|I
B
C
[w1]| , |I
B
C
[w2]| , |I
B
C
[w3]|}
Ir
C
= max {|I
C
C
[w1]| , |I
C
C
[w2]| , |I
C
C
[w3]|}
EXAMPLE
Consider a typical Wye/Delta power transformer with the following data:
Winding 1: CT Bank 1 – J1 = 500/5 CT ratio
Winding 2: CT Bank 2 – K1 = 1500/5 CT ratio
Transformer is 50% loaded
Magnitude Compensation
Based on 50% loading the winding currents are calculated as follows:
Winding 1 load current: I
load
(W1) = 2.5MVA/(3 * 13.8kV) = 104.5 Amps
Winding 2 load current: I
load
(W2) = 2.5MVA/(3 * 4.16kV) = 347 Amps
Since Winding 1 is always magnitude compensation reference, the currents from winding
1 , are scaled only to be presented in times Winding 1 CT.
M
W1
= 1 , - magnitude compensation factor for winding 1 - REFERENCE
Winding 1 currents = (M
W1
*I
load
(W
1
))/CT
W1
= 104.5/500 = 0.209 x CT
W1

Table of Contents

Related product manuals