EasyManua.ls Logo

GE 845 - Page 216

GE 845
552 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4–88 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
SYSTEM CHAPTER 4: SETPOINTS
Magnitude compensation for winding 2 currents:
M
W2
= (CT
W2
.V
W2
)/ (CT
W1
.V
W1
) = (1500*4.16)/(500*13.8) = 0.9043, -magnitude comp.
factor for Winding 2 currents
Winding 2 currents = (M
W2
* I
load
(W
2
))/CT
W2
= (0.9043*347)/1500 = 0.209 x CT
W2
To check that the measured currents from both windings will sum-up to zero after
applying magnitude compensation, one can perform the following simple calculations:
Phase Shift Compensation
From the transformer example, the phase reference winding is winding 2 (i.e.,w
f
= 2). The
phase compensation angle for each winding is then calculated as follows (Rotation =
“ABC):
φ
comp
[1] = -30°– 0° = -30° = 30° lag
φ
comp
[2] = -30° – (–30°) = 0°
The non-reference Wye winding will be rotated by -30° degrees to be in-phase and match
the currents from the Delta winding.
Per figure: Two-winding transformer connections for phase compensation angle of 30 lag,
the relay will use the following phase and zero-sequence compensation equations:
Winding 1 (Wye – grounded neutral):
I
A
p
[w]= (1/3)I
A
[w] - (1/3)I
C
[w]
I
B
p
[w]= (1/3)I
B
[w] - (1/3)I
A
[w]
I
C
p
[w]= (1/3)I
C
[w] - (1/3)I
B
[w]
Winding 2 (Delta):
I
A
p
[w] = I
A
[w]
I
B
p
[w] = I
B
[w]
I
C
p
[w]= I
C
[w]
The complete compensated winding 1 and winding 2 currents would be as follows:
The differential and restraint currents would be as follows:
Differential currents:
Id
A
= 0 x CT
Id
B
= 0 x CT
Id
C
= 0 x CT
Restraint currents:
Ir
A
= 0.209 x CT
Ir
B
= 0.209 x CT
Ir
C
= 0.209 x CT

Table of Contents

Related product manuals