Relay outputs:
Programmable relay outputs 2 Form C
Relay 01 Terminal number 1-3 (break), 1-2 (make)
Max. terminal load (AC-1)
1)
on 1-3 (NC), 1-2 (NO) (Resistive load) 240V AC, 2A
Max. terminal load (AC-15)
1)
(Inductive load @ cosφ 0.4) 240V AC, 0.2A
Max. terminal load (DC-1)
1)
on 1-2 (NO), 1-3 (NC) (Resistive load) 60V DC, 1A
Max. terminal load (DC-13)
1)
(Inductive load) 24 V DC, 0.1A
Relay 02 Terminal number 4-6 (break), 4-5 (make)
Max. terminal load (AC-1)
1)
on 4-5 (NO) (Resistive load)
2)3)
Overvoltage cat. II 400V AC, 2A
Max. terminal load (AC-15)
1)
on 4-5 (NO) (Inductive load @ cosφ 0.4) 240V AC, 0.2A
Max. terminal load (DC-1)
1)
on 4-5 (NO) (Resistive load) 80V DC, 2A
Max. terminal load (DC-13)
1)
on 4-5 (NO) (Inductive load) 24 V DC, 0.1A
Max. terminal load (AC-1)
1)
on 4-6 (NC) (Resistive load) 240V AC, 2A
Max. terminal load (AC-15)
1)
on 4-6 (NC) (Inductive load @ cosφ 0.4) 240V AC, 0.2A
Max. terminal load (DC-1)
1)
on 4-6 (NC) (Resistive load) 50V DC, 2A
Max. terminal load (DC-13)
1)
on 4-6 (NC) (Inductive load) 24 V DC, 0.1A
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO) 24V DC 10mA, 24V AC 20mA
Environment according to EN 60664-1 overvoltage category III/pollution degree 2
1)
IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2)
Overvoltage Category II
3)
UL applications 300V AC2A
Cable lengths and cross-sections for control cables:
Max. motor cable length, shielded 492 ft [150 m]
Max. motor cable length, non-shielded 984 ft [300 m]
Maximum cross-section to control terminals, flexible/ rigid wire without cable end sleeves 1.5mm
2
/16 AWG
Maximum cross-section to control terminals, flexible wire with cable end sleeves 1mm
2
/18 AWG
Maximum cross-section to control terminals, flexible wire with cable end sleeves with collar 0.5mm
2
/20 AWG
Minimum cross-section to control terminals 0.25mm
2
/ 24AWG
Control card performance:
Scan interval 1 ms
Control characteristics:
Resolution of output frequency at 0–1000Hz ± 0.003Hz
Repeat accuracy of Precise start/stop (terminals 18, 19) ≤± 0.1ms
System response time (terminals 18, 19, 27, 29, 32, 33) ≤ 2ms
Speed control range (open-loop) 1:100 of synchronous speed
Speed control range (closed-loop) 1:1000 of synchronous speed
Speed accuracy (open-loop) 30–4000 rpm: error ±8rpm
Speed accuracy (closed-loop), depending on resolution of feedback device 0–6000 rpm: error ±0.15 rpm
Torque control accuracy (speed feedback) max error±5% of rated torque
All control characteristics are based on a 4-pole asynchronous motor
Specifications AF-650 GP Quick Guide
36 DET-759A
8