EasyManua.ls Logo

GE AF-650 GP - Module-Level Static Test Procedures; Inverter Module Static Tests; Rectifier Module Static Tests; Soft Charge Rectifier Circuit Test

GE AF-650 GP
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AF-650 GP trifásico Tamaño de fusible recomendado Fusible máx. recomendado
kW / CV
0,37 / 1 / 2
gG-20 gG-32
0,75 / 1
1,5 / 2
2,2 / 3
3,7 / 5
5,5 / 7,5
7,5 / 10
11 / 15
gG-50 gG-80
15 / 20
18,5 / 25
gG-80 gG-100
22 / 30
30 / 40
gG-125 gG-16037 / 50
45 / 60
55 / 75
aR-250 aR-250
75 / 100
90 / 125 gG-300 gG-300
110 / 150 gG-350 gG-350
132 / 200 gG-400 gG-400
160 / 250 gG-500 gG-500
200 / 300 gG-630 gG-630
250 / 350 aR-700 aR-700
315 / 450
aR-900 aR-900355 / 500
400 / 550
450 / 600
aR-1600 aR-1600
500 / 650
560 / 750
aR-2000 aR-2000
630 / 900
710 / 1000
aR-2500 aR-2500
800 / 1200
Tabla 9.4 380-480 V IP55 / Nema 12 e IP66 / Nema 4
AF-650 GP trifásico Tamaño de fusible recomendado Fusible máx. recomendado
kW / CV
0,75 / 1
gG-10 gG-25
1,5 / 2
2,2 / 3
3,7 / 5
5,5 / 7,5
gG-16 gG-32
7,5 / 10
11 / 15
gG-35 gG-63
15 / 20
18,5 / 25
gG-63 gG-12522 / 30
30 / 40
37 / 50
gG-100 gG-150
45 / 60
55 / 75
aR-250 aR-250
75 / 100
Tabla 9.5 525-600 V IP20 / Chasis abierto