GE AK-15 - Installing the Insulator Bracket and Wire Harness

GE AK-15
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION
6
EQUIPMENT
CONVERSION
Installing
the
Insulator
Bracket
and
Wire
Harness
Mount
insulator
bracket
to
the
lower
right
corner
of
the
back
frame
utilizing
existing
holes
.
Refer
to
Fig
.
6
-
4
.
The
wire
harness
installation
depends
on
whether
the
breaker
is
a
3
-
wire
or
4
-
wire
,
draw
out
or
stationary
system
:
Step
.
1
For
all
draw
out
and
stationary
breakers
with
3
-
wire
systems
,
with
and
without
ground
fault
,
refer
to
Fig
.
6
-
4
.
Connect
the
A
,
B
,
and
C
phase
sensor
leads
respectively
to
TB
1
,
TB
2
and
TB
3
.
Identify
by
Table
6
-
1
.
Step
2
.
For
all
four
-
wire
draw
out
breakers
,
connect
the
ground
fault
lead
to
the
4
th
wire
disconnect
block
.
Step
3
.
For
all
four
-
wire
stationary
breakers
,
connect
the
ground
fault
lead
to
the
4
lh
wire
terminal
block
.
Fig
.
6
-
4
.
Back
Frame
Wire
Harness
Table
6
-
1
.
Harness
Connections
To
Harness
Connector
Pin
Number
From
Terminal
Board
Wire
Color
Component
TB
1
White
Black
18
Phase
A
Sensor
22
TB
2
White
Black
19
Phase
B
Sensor
23
TB
3
White
Black
20
Phase
C
Sensor
24
Flux
shift
Trip
Device
Trip
Device
32
Red
White
28
4
th
-
wire
Neutral
*
Sensor
TB
5
or
Secondarv
White
Black
21
17
*
Used
only
with
4
-
wire
Ground
Fault
23
Courtesy of NationalSwitchgear.com