EasyManua.ls Logo

GE AK-15 - Testing and Troubleshooting; Testing; Troubleshooting; False Tripping Breakers Equipped with Ground Fault

GE AK-15
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
False
Tripping
Breakers
Equipped
with
Ground
Fault
When
nuisance
tripping
occurs
on
breakers
equipped
with
the
ground
fault
trip
element
,
a
probable
cause
is
the
existence
of
a
false
ground
signal
.
Each
phase
sensor
is
connected
to
summing
circuitry
in
the
programmer
.
Under
no
-
fault
condi
-
tions
on
3
-
wire
load
circuits
,
the
currents
add
to
zero
,
and
no
ground
signal
is
developed
.
This
cur
-
rent
sum
will
be
zero
only
if
all
three
sensors
have
the
same
electrical
characteristics
.
If
one
sensor
dif
-
fers
from
the
others
(
i
.
e
.
,
different
rating
or
wrong
tap
setting
)
,
the
circuitry
can
produce
output
suffi
-
cient
to
trip
the
breaker
.
Similarly
,
discontinuity
be
-
tween
any
sensor
and
the
programmer
unit
can
cause
a
false
trip
signal
.
The
sensors
and
their
connections
should
be
closely
examined
if
nuisance
tripping
is
encountered
on
any
breaker
whose
MicroVersaTrip
®
Plus
or
PM
components
have
previously
demonstrated
satisfac
-
tory
performance
.
After
disconnecting
the
breaker
from
all
power
sources
,
perform
the
following
steps
:
Step
1
.
Check
that
all
phase
sensors
are
the
same
type
(
am
-
pere
range
)
.
Step
2
.
Make
sure
that
the
tap
settings
on
all
three
-
phase
sensors
are
identical
.
Step
3
.
Verify
that
the
harness
connections
to
the
sensors
meet
the
polarity
constraints
indicated
by
the
ca
-
bling
diagram
,
Fig
.
8
-
1
.
SECTION
8
TESTING
AND
TROUBLESHOOTING
Once
the
breaker
has
been
converted
,
but
before
it
is
energized
,
it
must
be
tested
.
See
below
for
troubleshooting
details
.
TESTING
Before
installing
a
converted
breaker
back
into
ser
-
vice
,
perform
the
following
steps
:
Step
1
.
Verify
that
the
programmer
is
securely
installed
.
The
phase
sensors
must
not
be
energized
if
they
are
open
-
circuited
.
Step
2
.
Megger
the
breaker
primary
circuit
using
a
1
,
000
-
Volt
Megger
.
Step
3
.
To
verify
that
the
breaker
has
been
properly
retro
-
fitted
,
a
primary
injection
test
should
be
performed
on
each
phase
.
This
test
will
check
the
CTs
,
bus
,
wir
-
ing
harness
,
flux
shifter
,
and
trip
unit
as
a
complete
system
.
A
high
current
,
low
voltage
power
supply
should
be
connected
across
each
line
and
load
ter
-
minal
to
simulate
an
overcurrent
fault
.
The
pro
-
grammer
long
-
time
may
be
set
at
0.5
to
minimize
the
breaker
stress
.
When
ground
fault
is
installed
,
the
test
can
be
performed
by
wiring
two
adjacent
poles
in
series
.
This
will
prevent
the
breaker
from
tripping
due
to
an
unbalance
current
flow
.
Do
not
attempt
to
use
test
kit
Cat
.
No
.
TVTS
1
or
TVRMS
on
this
programmer
.
TROUBLESHOOTING
When
malfunctioning
is
suspected
,
first
examine
the
circuit
breaker
and
its
power
system
for
abnor
-
mal
conditions
such
as
:
1
.
Breaker
not
tripping
in
proper
response
to
overcurrents
or
incipient
ground
faults
.
2
.
Breaker
remaining
in
a
trip
-
free
state
due
to
me
-
chanical
interference
along
its
trip
shaft
.
3
.
Inadvertent
shunt
trip
activations
.
WARNING
:
Do
not
change
taps
on
the
current
sensors
or
adjust
the
trip
unit
settings
while
the
breaker
is
earning
current
.
25
Courtesy of NationalSwitchgear.com

Related product manuals