EasyManua.ls Logo

GE AK-50 Series - Power Sensor Trip Maintenance

GE AK-50 Series
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Low
Voltage
Power
Circuit
Breakers
GEK
-
7303
REVERSE
CURRENT
TRIPPING
DEVICE
AK
-
SO
ONLY
(
Fig
.
31
)
The
device
is
enclosed
in
a
molded
case
and
is
mounted
on
the
right
pole
base
similar
to
the
series
overcurrent
tripping
device
.
The
reverse
current
tripping
device
(
see
Fig
.
28
)
consists
of
a
series
coil
(
2
)
with
an
iron
core
mount
-
ed
between
two
pole
pieces
(
9
)
,
also
a
potential
coil
(
7
)
connected
across
a
constant
source
of
voltage
and
mounted
around
a
rotary
-
type
arm
-
ature
(
10
)
.
Calibration
spring
(
6
)
determines
the
armature
pick
-
up
when
a
reversal
of
current
occurs
.
REPLACEMENT
(
Fig
.
31
)
After
removing
the
wiring
for
the
potential
coil
the
reverse
current
device
can
be
removed
and
replaced
by
following
the
procedure
outlined
for
replacing
the
series
over
current
device
.
For
wiring
,
see
Fig
.
31
)
.
POWER
SENSOR
TRIP
GENERAL
DESCRIPTION
All
AK
-
3
Type
Air
Circuit
Breakers
contain
Power
Sensor
Overcurrent
Trip
Devices
.
Power
Sensor
Trip
functions
with
solid
state
components
with
the
exception
of
the
Solenoid
Trip
which
is
used
to
trip
the
breaker
on
signal
from
the
Power
Sensor
Unit
.
The
Power
Sensor
Overcurrent
Trip
Device
consists
of
four
major
components
.
The
As
long
as
the
flow
of
current
through
the
breaker
is
in
the
normal
direction
,
the
magnetic
flux
of
the
series
coil
and
the
magnetic
flux
of
the
potential
coil
produce
a
torque
which
tends
to
rotate
the
armature
counterclockwise
.
The
calib
-
ration
spring
also
tends
to
rotate
the
armature
in
the
same
direction
.
This
torque
causes
the
armature
to
rest
against
the
stop
screw
(
12
)
attached
to
a
bearing
plate
on
the
right
side
of
the
device
.
If
the
current
through
the
series
coil
(
2
)
is
reversed
,
the
armature
(
10
)
tends
to
move
in
the
clockwise
direction
against
the
restraint
of
the
calibration
spring
(
6
)
.
When
the
current
reversal
exceeds
the
calibration
setting
,
the
armature
revolves
clockwise
causing
the
trip
rod
(
3
)
to
move
upward
engaging
the
trip
paddle
(
1
)
,
there
-
by
tripping
the
breaker
.
ADJUSTMENTS
(
Fig
.
31
)
The
only
adjustment
to
be
made
on
the
reverse
current
device
is
to
make
sure
that
the
trip
rod
has
a
minimum
overtravel
of
1
/
32
in
.
beyond
the
point
of
tripping
the
breaker
.
This
adjustment
should
have
to
be
made
only
when
an
old
device
is
being
replaced
by
a
new
one
.
The
new
device
will
be
factory
adjusted
so
that
the
top
end
of
the
trip
rod
(
3
)
will
extend
1
/
2
in
.
above
the
top
of
the
device
case
,
and
no
addi
-
tional
adjustments
of
the
trip
rod
should
be
required
.
To
obtain
the
proper
1
/
32
in
.
over
-
travel
,
close
the
breaker
and
proceed
as
follows
:
1
.
Loosen
the
locking
nut
(
2
B
)
.
2
.
Manually
lift
the
trip
rod
and
vary
the
position
of
the
adjusting
nut
(
2
A
)
,
this
establish
-
ing
the
position
of
the
adjusting
nut
where
the
breaker
is
just
tripped
.
NOTE
:
Be
sure
to
keep
clear
of
moving
breaker
parts
when
tripping
the
breaker
.
3
.
With
this
position
of
the
adjusting
nut
established
,
advance
the
adjusting
nut
upward
one
and
one
-
half
turns
.
4
.
Tighten
the
locking
nut
and
the
minimum
1
/
32
-
in
.
overtravel
of
the
trip
rod
should
be
obtained
.
1
»
The
magnetic
coils
around
the
breaker
conductors
(
Fig
.
32
&
33
)
.
2
.
The
Power
Supply
which
provides
both
the
tripping
energy
and
the
comparison
basis
for
overcurrent
detection
(
Fig
.
34
)
.
3
.
The
Power
Sensor
Unit
with
the
various
pick
-
up
settings
and
time
delay
selection
taps
(
Fig
.
35
)
.
4
.
The
trip
solenoid
which
physically
trips
the
breaker
(
Fig
.
36
)
.
In
addition
to
the
phase
overcurrent
protection
,
a
ground
fault
sensing
feature
may
be
provided
.
The
Ground
Sensing
Device
works
on
the
principle
that
the
instantaneous
value
of
current
flowing
in
the
three
conductors
(
or
;
in
four
conductors
on
four
wire
systems
)
must
add
to
zero
unless
ground
current
is
flowing
.
Therefore
,
if
the
electrical
system
is
a
four
wire
wye
system
with
the
neutral
grounded
at
the
transformer
,
the
fourth
sensing
coil
Fig
.
38
must
be
included
on
the
neutral
conductor
with
its
secondary
combined
with
the
secondaries
of
the
three
phase
sensors
which
are
mounted
on
the
breaker
.
On
Draw
-
out
breakers
the
output
of
the
external
neutral
sensor
must
enter
the
breaker
by
a
control
disconnect
which
is
mounted
low
and
on
the
centerline
on
the
back
of
the
breaker
.
Refer
to
Fig
.
(
37
)
for
Power
Sensor
Cabling
Diagram
.
MAINTENANCE
When
mal
-
functioning
of
thePower
Sensor
Trip
is
indicated
,
the
trouble
should
be
traced
to
one
or
more
of
these
four
components
involved
,
and
that
component
should
be
replaced
as
a
unit
.
The
following
steps
should
be
taken
to
detect
a
mal
-
functioning
unit
.
No
adjustment
to
the
taps
controlling
NOTE
:
pick
-
up
should
be
made
with
the
breaker
car
-
rying
current
.
In
the
event
the
Power
Sensor
Device
must
be
made
non
-
operative
to
allow
the
breaker
to
33
Courtesy of NationalSwitchgear.com

Related product manuals