Low
Voltage
Power
Circuit
Breakers
GEK
-
7303
5
.
Push
wire
through
hollow
tube
of
new
disconnect
assembly
.
6
.
Strip
insulation
off
end
of
wire
to
about
1
/
4
in
.
from
the
end
.
7
.
Place
new
contact
tip
on
end
of
wire
and
crimp
.
8
.
Pull
wire
through
hollow
tube
until
contact
tip
fits
snugly
against
end
of
hollow
tube
.
9
.
Crimp
tab
on
other
side
of
assembly
to
hold
wire
in
place
.
10
.
Any
hollow
tubes
which
are
not
used
should
be
pushed
into
the
disconnect
body
and
held
in
that
position
by
placing
fiber
spacers
over
inner
ends
of
tubes
and
spreading
tabs
.
11
.
When
all
wires
have
been
connected
,
refasten
the
body
of
the
movable
disconnect
assembly
to
the
breaker
cross
-
channel
.
Fig
.
43
(
8026230
)
Typical
drawout
mechanism
1
.
Racking
Handle
2
.
Link
3
.
Pin
4
.
Racking
Cam
DRAWOUT
MECHANISM
(
FIG
.
43
)
Drawout
breakers
are
furnished
with
a
drawout
mechanism
which
facilitates
the
inserting
and
withdrawing
of
the
breaker
from
its
enclosure
.
It
provides
a
suitable
menas
of
forcing
the
breaker
through
the
part
of
the
inserting
and
withdrawal
operations
when
the
stationary
and
movable
halves
of
the
disconnects
engage
and
disengage
.
For
complete
details
of
inserting
and
withdrawing
the
breaker
,
such
as
the
number
of
racking
handle
strokes
required
to
install
or
withdraw
the
breaker
,
refer
to
instruction
cJEK
-
7302
furnished
with
the
breaker
.
The
drawout
mechanism
is
equipped
with
a
drawout
trip
interlock
which
prevents
a
racking
operation
from
being
performed
when
the
breaker
is
closed
.
Inserting
the
breaker
into
the
housing
causes
the
racking
pins
on
the
housing
to
engage
the
semi
-
circular
slot
in
the
racking
cam
(
4
)
.
In
this
position
the
breaker
is
ready
to
be
fully
racked
-
in
by
operating
the
racking
handle
(
1
)
.
The
first
upward
stroke
of
the
racking
handle
causes
the
racking
pin
on
the
housing
to
engage
the
trip
interlock
link
and
pin
assembly
(
2
,
3
)
,
rotating
the
link
(
2
)
and
causing
the
pin
(
3
)
to
move
upward
against
the
adjusting
screw
on
the
interlock
trip
paddle
.
This
trips
the
breaker
and
holds
it
trip
-
free
during
the
entire
racking
opera
-
tion
.
The
fifth
and
final
stroke
of
the
racking
handle
releases
the
trip
interlock
and
allows
the
breaker
to
be
closed
,
since
the
breaker
is
now
fully
racked
-
in
.
ADJUSTMENTS
(
Fig
.
43
)
One
adjustment
on
the
trip
interlock
is
re
-
quired
.
With
the
breaker
mechanism
in
the
re
-
set
position
and
the
racking
cam
(
4
)
not
engaging
the
racking
pins
on
the
housing
,
there
should
be
at
least
l
/
8
in
.
of
the
trip
interlock
pin
(
3
)
and
the
adjusting
screw
on
the
interlock
trip
.
Fig
.
44
(
8039672
)
AK
-
3
A
-
50
1
.
Racking
Pins
The
Drawout
Mechanism
for
AK
-
2
A
/
3
A
-
50
,
75
,
100
Breakers
is
located
in
the
equipment
.
Four
racking
pins
(
1
)
Fig
.
44
,
two
on
either
side
of
the
breaker
are
furnished
to
facilitate
the
drawout
mechanism
tray
in
the
equipment
.
clearance
between
the
top
edge
43