Magne
-
blast
Circuit
Breaker
GE
1
-
88761
Figure
14
.
(
8034464
)
Plunger
Interlock
1
.
Plunger
Bolt
Washer
Breaker
Lifting
Rail
Figure
13
.
(
0114
C
5320
)
Latch
Checking
Switch
1
.
Switch
Support
2
.
Latch
Checking
Switch
3
.
Switch
Arm
4
.
Trip
Latch
5
.
Reset
Pin
Stop
6
.
Latch
Roller
7
.
Latch
Roller
Link
8
.
Latch
Roller
Pin
to
open
the
latch
checking
switch
(
2
)
.
Allow
the
trip
latch
to
reset
slowly
and
determine
fee
point
at
which
the
contacts
are
made
by
using
a
circuit
continuity
tester
(
light
indicator
,
bell
set
,
etc
)
.
The
contacts
of
the
latch
checking
switch
should
just
make
when
the
gap
between
the
trip
latch
(
4
)
and
the
stop
pin
(
5
)
located
on
the
latch
roller
link
(
7
)
is
1
/
16
"
.
There
should
be
a
minimum
of
1
/
64
"
between
the
switch
arm
(
3
)
and
the
switch
support
(
1
)
.
To
obtain
adjustment
of
the
latch
check
-
switch
,
bend
the
latch
checking
switch
arm
Figure
15
.
(
8034471
)
Driving
Elements
1
.
Mounting
Bolts
Manual
Close
Button
3
.
Eccentric
4
.
Retaining
Ring
5
.
Hex
Charging
Stud
6
.
Driving
Link
7
.
Motor
Support
8
.
Retaining
Ring
9
.
Motor
Fuse
2
.
ing
(
3
J
.
10
.
Plunger
Interlock
Refer
to
Figure
14
.
With
the
breaker
in
the
closed
position
,
the
vertical
distance
"
A
"
from
the
top
of
the
plunger
bolt
(
1
)
to
the
bottom
of
the
breaker
lifting
rail
(
3
)
should
be
16
-
19
/
32
"
to
16
-
23
/
32
"
.
To
change
this
adjustment
,
add
or
remove
washers
(
2
)
.
Inspection
and
Test
1
.
For
ease
in
reviewing
the
adjustments
,
the
following
are
recapitulated
:
a
.
Primary
contact
wipe
:
1
/
4
"
to
5
/
16
"
.
b
.
Arcing
contact
wipe
:
5
/
16
"
or
greater
gap
at
primary
contacts
.
c
.
Primary
contactgap
:
3
-
5
/
8
"
to
3
-
15
/
16
'
.
'
d
.
Trip
latch
wipe
:
3
/
16
"
to
1
/
4
"
with
trip
latch
resting
against
stop
pin
.
e
.
Trip
armature
travel
7
/
32
"
to
9
/
32
"
.
f
.
Release
latch
wipe
:
3
/
16
"
to
1
/
4
"
.
Release
latch
monitoring
switch
:
Max
-
imum
clearance
1
/
32
"
.
Auxiliary
Fuses
Refer
to
Figure
15
.
On
breakers
with
a
"
C
"
or
"
K
"
suffix
,
a
set
of
protecting
fuses
(
10
)
are
mounted
on
the
front
of
fee
breaker
.
These
fuses
are
the
primary
protective
devices
for
the
closing
control
circuit
on
those
breakers
that
are
used
in
metal
-
clad
units
designed
for
solenoid
operated
breakers
.
g
-
13
Courtesy of store.ips.us