2-84 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
Capacitor Bank Overvoltage Actuals (Read Only) (3 Modules)
C70 6390 Bank Overvoltage 1 Phase A Operate
Voltage
0 to 65.535 pu 0.001 F001 0
" 6391 Bank Overvoltage 1 Phase B Operate
Voltage
0 to 65.535 pu 0.001 F001 0
" 6392 Bank Overvoltage 1 Phase C Operate
Voltage
0 to 65.535 pu 0.001 F001 0
" 6393 ...Repeated for Bank Overvoltage 2
" 6396 ...Repeated for Bank Overvoltage 3
Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 or 3 Modules)
C70, D30, D60,
F35, F60, L30,
L60, L90, T60
63C0 Negative Sequence Instantaneous OC 1
Function
0 to 1 --- 1 F102 0 (Disabled)
" 63C1 Negative Sequence Instantaneous OC 1
Signal Source
0 to 5 --- 1 F167 0 (SRC 1)
" 63C2 Negative Sequence Instantaneous
Overcurrent 1 Pickup
0.02 to 30 pu 0.001 F001 1000
" 63C3 Negative Sequence Instantaneous
Overcurrent 1 Delay
0 to 600 s 0.01 F001 0
" 63C4 Negative Sequence Instantaneous OC 1
Reset Delay
0 to 600 s 0.01 F001 0
" 63C5 Negative Sequence Instantaneous
Overcurrent 1 Block
0 to 4294967295 --- 1 F300 0
" 63C7 Negative Sequence Instantaneous
Overcurrent 1 Target
0 to 2 --- 1 F109 0 (Self-reset)
" 63C8 Negative Sequence Instantaneous
Overcurrent 1 Events
0 to 1 --- 1 F102 0 (Disabled)
" 63C9 Reserved (8 items) 0 to 1 --- 1 F001 0
" 63D1 ...Repeated for Negative Sequence
Instantaneous OC 2
T60 63E2 ...Repeated for Negative Sequence
Instantaneous OC 3
Current Unbalance (Read/Write Grouped Setting) (2 Modules)
M60 6400 Current Unbalance 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 6401 Current Unbalance 1 Pickup 0.1 to 100 % 0.1 F001 400
" 6402 Current Unbalance 1 Pickup Delay 0 to 600 s 0.01 F001 0
" 6403 Current Unbalance 1 Reset Delay 0 to 600 s 0.01 F001 0
" 6404 Current Unbalance 1 Block 0 to 4294967295 --- 1 F300 0
" 6406 Current Unbalance 1 Targets 0 to 2 --- 1 F109 0 (Self-reset)
" 6407 Current Unbalance 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 6408 Current Unbalance 1 Reserved (5 items) 0 to 1 --- 1 F001 0
" 640D ...Repeated for Current Unbalance 2
Stator Differential (Read/Write Grouped Setting)
G60, M60 6420 Stator Differential Function 0 to 1 --- 1 F102 0 (Disabled)
" 6421 Stator Differential Pickup 0.05 to 1 pu 0.001 F001 100
" 6422 Stator Differential Slope 1 1 to 100 % 1 F001 10
" 6423 Stator Differential Slope 2 1 to 100 % 1 F001 80
" 6424 Stator Differential Break 1 1 to 1.5 pu 0.01 F001 115
" 6425 Stator Differential Break 2 1.5 to 30 pu 0.01 F001 800
" 6426 Stator Differential Block 0 to 4294967295 --- 1 F300 0
" 6428 Stator Differential Targets 0 to 2 --- 1 F109 0 (Self-reset)
Products Address Register name Range Units Step Format Default