CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-85
2
" 6429 Stator Differential Events 0 to 1 --- 1 F102 0 (Disabled)
" 642A Stator Differential Line End Source 0 to 5 --- 1 F167 0 (SRC 1)
" 642B Stator Differential Neutral End Source 0 to 5 --- 1 F167 0 (SRC 1)
Negative Sequence Overvoltage (Read/Write Grouped Setting) (3 Modules)
C70, D30, D60,
F60, G30, G60,
L30, L60, M60,
T60
6440 Negative Sequence Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 6441 Negative Sequence Overvoltage 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
" 6442 Negative Sequence Overvoltage 1 Pickup 0.004 to 1.25 pu 0.001 F001 300
" 6443 Negative Sequence Overvoltage 1 Pickup
Delay
0 to 600 s 0.01 F001 50
" 6444 Negative Sequence Overvoltage 1 Reset
Delay
0 to 600 s 0.01 F001 50
" 6445 Negative Sequence Overvoltage 1 Block 0 to 4294967295 --- 1 F300 0
" 6447 Negative Sequence Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6448 Negative Sequence Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 6449 ...Repeated for Negative Sequence
Overvoltage 2
" 6452 ...Repeated for Negative Sequence
Overvoltage 3
Overfrequency (Read/Write Setting) (4 Modules)
C60, D60, F60,
G30, G60, L90,
M60, N60, T60
6470 Overfrequency 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 6471 Overfrequency 1 Block 0 to 4294967295 --- 1 F300 0
" 6473 Overfrequency 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
" 6474 Overfrequency 1 Pickup 20 to 65 Hz 0.01 F001 6050
" 6475 Overfrequency 1 Pickup Delay 0 to 65.535 s 0.001 F001 500
" 6476 Overfrequency 1 Reset Delay 0 to 65.535 s 0.001 F001 500
" 6477 Overfrequency 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6478 Overfrequency 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 6479 Reserved (4 items) 0 to 1 --- 1 F001 0
" 647D ...Repeated for Overfrequency 2
" 648A ...Repeated for Overfrequency 3
" 6497 ...Repeated for Overfrequency 4
Bus Configuration (Read/Write Setting) (2 Modules)
B30 64B0 Bus Zone 1A Source (6 items 1A to 1F) 0 to 5 --- 1 F167 0 (SRC 1)
" 64B6 Bus Zone 1A Status (6 items 1A to 1F) 0 to 4294967295 --- 1 F300 0
" 64C2 ...Repeated for Bus Zone 2
Bus Differential (Read/Write Grouped Setting) (2 or 6 Modules)
B30, B90 64E0 Bus Zone 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 64E1 Bus Zone 1 Pickup 0.05 to 6 pu 0.001 F001 100
" 64E2 Bus Zone 1 Low Slope 15 to 100 % 1 F001 25
" 64E3 Bus Zone 1 Low Breakpoint 1 to 30 pu 0.01 F001 200
" 64E4 Bus Zone 1 High Slope 50 to 100 % 1 F001 60
" 64E5 Bus Zone 1 High Breakpoint 1 to 30 pu 0.01 F001 800
" 64E6 Bus Zone 1 High Set 0.1 to 99.99 pu 0.01 F001 1500
" 64E7 Bus Zone 1 Seal In 0 to 65.535 s 0.001 F001 400
" 64E8 Bus Zone 1 Block 0 to 4294967295 --- 1 F300 0
Products Address Register name Range Units Step Format Default