2-86 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" 64EA Bus Zone 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 64EB Bus Zone 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
B90 64EC Bus Zone 1 Supervision 0 to 4294967295 --- 1 F300 1
B90 64F6 Bus Zone 1 Trip 0 to 4294967295 --- 1 F300 0
B30, B90 64F8 ...Repeated for Bus Zone 2
B90 6510 ...Repeated for Bus Zone 3
" 6528 ...Repeated for Bus Zone 4
" 6540 ...Repeated for Bus Zone 5
" 6558 ...Repeated for Bus Zone 6
Time of Day Timer (Read/Write Setting) (5 Modules)
C70 6570 Time of Day Timer 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 6571 Time of Day Timer 1 Start Time 0 to 2359 --- 1 F050 0
" 6573 Time of Day Timer 1 Stop Time 0 to 2359 --- 1 F050 2359
" 6575 Time of Day Timer 1 Targets 0 to 2 --- 1 F109 0 (Self-reset)
" 6576 Time of Day Timer 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 6577 ...Repeated for Time of Day Timer 2
" 657E ...Repeated for Time of Day Timer 3
" 6585 ...Repeated for Time of Day Timer 4
" 658C ...Repeated for Time of Day Timer 5
CT Trouble (Read/Write Setting) (2 or 6 Modules)
B30, B90 65A0 CT Trouble 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 65A1 CT Trouble 1 Pickup 0.02 to 2 pu 0.001 F001 100
" 65A2 CT Trouble 1 Delay 1 to 60 s 0.1 F001 100
" 65A3 CT Trouble 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 65A4 CT Trouble 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 65A5 ...Repeated for CT Trouble 2
B90 65AA ...Repeated for CT Trouble 3
" 65AF ...Repeated for CT Trouble 4
" 65B4 ...Repeated for CT Trouble 5
" 65B9 ...Repeated for CT Trouble 6
Bus Configuration (Read/Write Setting) (6 Modules)
B90 65BE Bus Zone x CT (24 items) 0 to 23 --- 1 F400 0
Power Swing Detect (Read/Write Grouped Setting)
D30, D60, G60,
L60, L90, N60,
T60
65C0 Power Swing Detect Function 0 to 1 --- 1 F102 0 (Disabled)
" 65C1 Power Swing Detect Source 0 to 5 --- 1 F167 0 (SRC 1)
" 65C2 Power Swing Detect Mode 0 to 1 --- 1 F513 0 (Two Step)
" 65C3 Power Swing Detect Supervision 0.05 to 30 pu 0.001 F001 600
" 65C4 Power Swing Detect Forward Reach 0.1 to 500 ohms 0.01 F001 5000
" 65C5 Power Swing Detect Forward RCA 40 to 90 degrees 1 F001 75
" 65C6 Power Swing Detect Reverse Reach 0.1 to 500 ohms 0.01 F001 5000
" 65C7 Power Swing Detect Reverse RCA 40 to 90 degrees 1 F001 75
" 65C8 Power Swing Detect Outer Limit Angle 40 to 140 degrees 1 F001 120
" 65C9 Power Swing Detect Middle Limit Angle 40 to 140 degrees 1 F001 90
" 65CA Power Swing Detect Inner Limit Angle 40 to 140 degrees 1 F001 60
" 65CB Power Swing Detect Delay 1 Pickup 0 to 65.535 s 0.001 F001 30
Products Address Register name Range Units Step Format Default