CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-87
2
" 65CC Power Swing Detect Delay 1 Reset 0 to 65.535 s 0.001 F001 50
" 65CD Power Swing Detect Delay 2 Pickup 0 to 65.535 s 0.001 F001 17
" 65CE Power Swing Detect Delay 3 Pickup 0 to 65.535 s 0.001 F001 9
" 65CF Power Swing Detect Delay 4 Pickup 0 to 65.535 s 0.001 F001 17
" 65D0 Power Swing Detect Seal In Delay 0 to 65.535 s 0.001 F001 400
" 65D1 Power Swing Detect Trip Mode 0 to 1 --- 1 F514 0 (Delayed)
" 65D2 Power Swing Detect Block 0 to 4294967295 --- 1 F300 0
" 65D4 Power Swing Detect Target 0 to 2 --- 1 F109 0 (Self-reset)
" 65D5 Power Swing Detect Event 0 to 1 --- 1 F102 0 (Disabled)
" 65D6 Power Swing Detect Shape 0 to 1 --- 1 F085 0 (Mho
Shape)
Bus Configuration (Read/Write Setting) (6 Modules)
B90 65D6 Bus Zone x Dir (24 items) 0 to 1 --- 1 F210 0 (IN)
Power Swing Detect (Read/Write Grouped Setting)
D30, D60, G60,
L60, L90, N60,
T60
65D7 Power Swing Detect Quad Forward Middle 0.1 to 500 ohms 0.01 F001 6000
" 65D8 Power Swing Detect Quad Forward Outer 0.1 to 500 ohms 0.01 F001 7000
" 65D9 Power Swing Detect Quad Reverse Middle 0.1 to 500 ohms 0.01 F001 6000
" 65DA Power Swing Detect Quad Reverse Outer 0.1 to 500 ohms 0.01 F001 7000
" 65DB Power Swing Detect Outer Right Blinder 0.1 to 500 ohms 0.01 F001 10000
" 65DC Power Swing Detect Outer Left Blinder 0.1 to 500 ohms 0.01 F001 10000
" 65DD Power Swing Detect Middle Right Blinder 0.1 to 500 ohms 0.01 F001 10000
" 65DE Power Swing Detect Middle Left Blinder 0.1 to 500 ohms 0.01 F001 10000
" 65DF Power Swing Detect Inner Right Blinder 0.1 to 500 ohms 0.01 F001 10000
" 65E0 Power Swing Detect Inner Left Blinder 0.1 to 500 ohms 0.01 F001 10000
" 65E1 Power Swing I2 Supervision Enable 0 to 4294967295 --- 1 F300 0
" 65E3 Power Swing I2 Supervision 0.05 to 30 pu 0.001 F001 200
Bus Configuration (Read/Write Setting) (6 Modules)
B90 65EE Bus Zone 1 Status (24 items) 0 to 4294967295 --- 1 F300 0
Motor Setup (Read/Write Setting)
M60 6600 Thermal Model Motor FLA 0.05 to 1 pu 0.001 F001 1000
" 6601 Thermal Model Motor Service (Overload)
Factor
1 to 1.5 --- 0.01 F001 100
" 6602 Thermal Model Line Source 0 to 5 --- 1 F167 0 (SRC 1)
" 6603 Thermal Model Motor Offline 0 to 4294967295 --- 1 F300 0
" 6605 Thermal Model RTD 1 0 to 48 --- 1 F151 0 (NONE)
" 6606 Thermal Model RTD 2 0 to 48 --- 1 F151 0 (NONE)
" 6607 Thermal Model RTD 3 0 to 48 --- 1 F151 0 (NONE)
" 6608 Thermal Model RTD 4 0 to 48 --- 1 F151 0 (NONE)
" 6609 Thermal Model RTD 5 0 to 48 --- 1 F151 0 (NONE)
" 660A Thermal Model RTD 6 0 to 48 --- 1 F151 0 (NONE)
" 660B Motor Emergency Restart 0 to 4294967295 --- 1 F300 0
" 660D Motor Nameplate Voltage 100 to 50000 V 1 F001 600
" 660E Speed 2 Motor Protection 0 to 1 --- 1 F102 0 (Disabled)
" 660F Speed 2 Motor Switch 0 to 4294967295 --- 1 F300 0
" 6611 Speed 2 Switch 2-1 Delay 0 to 600 s 0.01 F001 500
" 6612 Speed 2 Motor Source 0 to 5 --- 1 F167 0 (SRC 1)