2-88 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" 6613 Speed 2 Motor FLA 0.05 to 1 pu 0.001 F001 1000
Bus Configuration (Read/Write Setting) (6 Modules)
B90 661E ...Repeated for Bus Zone 2
Thermal Model Actual Values (Read Only)
M60 6630 Thermal Model Motor Status 0 to 3 --- 1 F098 1 (Starting)
" 6631 Thermal Model Capacity Used 0 to 100 % 1 F001 0
" 6633 Trip Time On Overload 0 to 10000 --- 1 F001 0
" 6634 Thermal Model Lockout Time 0 to 65000 min 1 F001 0
Thermal Model Actuals (Read Only)
M60 6638 Thermal Model Load 0 to 40 x FLA 0.01 F001 0
" 663A Thermal Model Motor Unbalance 0 to 100 % 1 F001 0
" 663B Thermal Model Biased Motor Load 0 to 40 x FLA 0.01 F001 0
" 663C Start/Hour Lockout Time 0 to 65000 min 1 F001 0
" 663D Time-Between-Starts Lockout Time 0 to 65000 min 1 F001 0
" 663E Restart Delay Lockout Time 0 to 65000 s 1 F001 0
" 663F Total Motor Lockout Time 0 to 65000 min 1 F001 0
Field Ground Actual Values (Read Only)
G60 6640 Field Ground Resistance 0 to 20000 kOhm 0.001 F003 20000000
" 6642 Field Ground Current 0 to 655.35 mA 0.01 F001 0
" 6643 Field Ground Injected Voltage -32.767 to 32.767 V 0.001 F002 0
" 6644 Field Ground Fault Location -30000 to 30000 % 1 F002 -10
" 6645 Field Ground Field Voltage -3276.8 to 3276.7 V 0.1 F002 0
" 6646 Field Current -9999.999 to
9999.999
--- 0.001 F004 0
" 6648 Field Current Units --- --- --- F206 "A"
Accidental Energization (Read/Write Grouped Setting)
G30, G60 6650 Accidental Energization Function 0 to 1 --- 1 F102 0 (Disabled)
" 6651 Accidental Energization Source 0 to 5 --- 1 F167 0 (SRC 1)
" 6652 Accidental Energization Arming Mode 0 to 1 --- 1 F193 0 (UV AND
OFFLINE)
" 6653 Accidental Energization OC Pickup 0.02 to 3 pu 0.001 F003 300
" 6655 Accidental Energization UV Pickup 0.004 to 3 pu 0.001 F003 500
" 6657 Accidental Energization Offline 0 to 4294967295 --- 1 F300 0
" 6659 Accidental Energization Block 0 to 4294967295 --- 1 F300 0
" 665B Accidental Energization Target 0 to 2 --- 1 F109 0 (Self-reset)
" 665C Accidental Energization Events 0 to 1 --- 1 F102 0 (Disabled)
" 665D Reserved (5 items) 0 to 65535 --- 1 F001 0
Loss of Excitation (Read/Write Grouped Setting)
G30, G60 666A Loss Of Excitation Function 0 to 1 --- 1 F102 0 (Disabled)
" 666B Loss Of Excitation Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
" 666C Loss Of Excitation Center 1 0.1 to 300 ohm 0.01 F001 1000
" 666D Loss Of Excitation Radius 1 0.1 to 300 ohm 0.01 F001 800
" 666E Loss Of Excitation UV Supervision Enable 1 0 to 1 --- 1 F102 1 (Enabled)
" 666F Loss Of Excitation Pickup Delay 1 0 to 65.535 s 0.001 F001 50
" 6670 Loss Of Excitation Center 2 0.1 to 300 ohm 0.01 F001 1200
" 6671 Loss Of Excitation Radius 2 0.1 to 300 ohm 0.01 F001 1000
" 6672 Loss Of Excitation UV Supervision Enable 2 0 to 1 --- 1 F102 1 (Enabled)
Products Address Register name Range Units Step Format Default