2-94 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" 6821 Hybrid POTT 1P Permissive Echo 0 to 2 --- 1 F199 0 (Disabled)
" 6822 Hybrid POTT 1P Rx Pickup Delay 0 to 65.535 s 0.001 F001 0
" 6823 Hybrid POTT 1P Trans Block Pickup Delay 0 to 65.535 s 0.001 F001 20
" 6824 Hybrid POTT 1P Trans Block Reset Delay 0 to 65.535 s 0.001 F001 90
" 6825 Hybrid POTT 1P Echo Duration 0 to 65.535 s 0.001 F001 100
" 6826 Hybrid POTT 1P Echo Lockout 0 to 65.535 s 0.001 F001 250
" 6827 Hybrid POTT 1P Seal In Delay 0 to 65.535 s 0.001 F001 0
" 6828 Hybrid POTT 1P Ground Directional
Overcurrent Forward
0 to 4294967295 --- 1 F300 0
" 682A Hybrid POTT 1P Gnd Directional
Overcurrent Reverse
0 to 4294967295 --- 1 F300 0
" 682C Hybrid POTT 1P Number of Communication
Bits
0 to 2 --- 1 F198 0 (1)
" 682D Hybrid POTT 1P Rx1 0 to 4294967295 --- 1 F300 0
" 682F Hybrid POTT 1P Rx2 0 to 4294967295 --- 1 F300 0
" 6831 Hybrid POTT 1P Rx3 0 to 4294967295 --- 1 F300 0
" 6833 Hybrid POTT 1P Rx4 0 to 4294967295 --- 1 F300 0
" 6835 Hybrid POTT 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6836 Hybrid POTT 1P Event 0 to 1 --- 1 F102 0 (Disabled)
" 6837 Hybrid POTT 1P Echo Condition 0 to 4294967295 --- 1 F300 0
" 6839 Hybrid POTT 1P Weak Infeed 0 to 2 --- 1 F199 1 (Enabled)
" 683A Hybrid POTT 1P Weak Infeed Condition 0 to 4294967295 --- 1 F300 0
" 683C Hybrid POTT 1P Block 0 to 4294967295 --- 1 F300 0
" 683E Reserved (3 items) 0 to 1 --- 1 F001 0
Pilot Blocking (1P) (Read/Write Setting)
D60, L90 6845 Blocking Scheme 1P Function 0 to 1 --- 1 F102 0 (Disabled)
" 6846 Block 1P Rx Coord Pickup Delay 0 to 65.535 s 0.001 F001 10
" 6847 Block 1P Transient Block Pickup Delay 0 to 65.535 s 0.001 F001 30
" 6848 Block 1P Transient Block Reset Delay 0 to 65.535 s 0.001 F001 90
" 6849 Blocking Scheme 1P Seal In Delay 0 to 65.535 s 0.001 F001 0
" 684A Blocking Scheme 1P Gnd Directional
Overcurrent Fwd
0 to 4294967295 --- 1 F300 0
" 684C Blocking Scheme 1P Gnd Directional
Overcurrent Rev
0 to 4294967295 --- 1 F300 0
" 684E Blocking Scheme 1P Number of
Communication Bits
0 to 2 --- 1 F198 0 (1)
" 684F Blocking Scheme 1P Rx1 0 to 4294967295 --- 1 F300 0
" 6851 Blocking Scheme 1P Rx2 0 to 4294967295 --- 1 F300 0
" 6853 Blocking Scheme 1P Rx3 0 to 4294967295 --- 1 F300 0
" 6855 Blocking Scheme 1P Rx4 0 to 4294967295 --- 1 F300 0
" 6857 Blocking 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6858 Blocking 1P Event 0 to 1 --- 1 F102 0 (Disabled)
" 6859 Blocking Scheme 1P Block 0 to 4294967295 --- 1 F300 0
" 685B Reserved (5 items) 0 to 1 --- 1 F001 0
Autoreclose 1P 3P (Read/Write Setting)
C60, D60, L60,
L90
6860 Autoreclose Mode 0 to 3 --- 1 F622 0 (Mode 1 (1
& 3 Pole))
" 6861 Autoreclose Maximum Number of Shots 1 to 4 --- 1 F001 2