CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-93
2
" 679D Phase Selector Reset 0 to 4294967295 --- 1 F300 0
" 679F Reserved (4 items) 0 to 1 --- 1 F001 0
Bus Configuration (Read/Write Setting) (6 Modules)
B90 679E ...Repeated for Bus Zone 6
Open Pole Detect (1P) (Read/Write Setting)
C60, D60, L60, 
L90
67B0 Open Pole Function 0 to 1 --- 1 F102 0 (Disabled)
" 67B1 Open Pole Block 0 to 4294967295 --- 1 F300 0
" 67B3 Open Pole Voltage Supervision 0 to 1 --- 1 F102 0 (Disabled)
" 67B4 Open Pole Current Pickup 0.02 to 30 pu 0.001 F001 50
" 67B5 Open Pole Target 0 to 2 --- 1 F109 0 (Self-reset)
" 67B6 Open Pole Events 0 to 1 --- 1 F102 0 (Disabled)
" 67B7 Open Pole Line XC0 300 to 9999.9 ohms 0.1 F003 99999
" 67B9 Open Pole Line XC1 300 to 9999.9 ohms 0.1 F003 99999
" 67BB Open Pole Remote Current Pickup 0.02 to 30 pu 0.001 F001 50
" 67BC Open Pole Detection 0 to 1 --- 1 F608 0 (I AND V 
AND CBaux)
" 67BD Open Pole Mode 0 to 1 --- 1 F607 0 
(Accelerated
)
" 67BE Reserved (3 items) 0 to 1 --- 1 F001 0
Pilot DUTT (1P) (Read/Write Setting)
D60, L90 67D0 DUTT Function 0 to 1 --- 1 F102 0 (Disabled)
" 67D1 DUTT Seal In Delay 0 to 65.535 s 0.001 F001 0
" 67D2 DUTT 1P Number of Communication Bits 0 to 2 --- 1 F198 0 (1)
" 67D3 DUTT RX1 0 to 4294967295 --- 1 F300 0
" 67D5 DUTT RX2 0 to 4294967295 --- 1 F300 0
" 67D7 DUTT RX3 0 to 4294967295 --- 1 F300 0
" 67D9 DUTT RX4 0 to 4294967295 --- 1 F300 0
" 67DB DUTT 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
" 67DC DUTT 1P Event 0 to 1 --- 1 F102 0 (Disabled)
" 67DD DUTT 1P Scheme Block 0 to 4294967295 --- 1 F300 0
" 67DF Reserved (6 items) 0 to 1 --- 1 F001 0
Pilot PUTT (1P) (Read/Write Setting)
D60, L90 67EA PUTT 1P Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
" 67EB PUTT 1P Rx Pickup Delay 0 to 65.535 s 0.001 F001 0
" 67EC PUTT 1P Seal In Delay 0 to 65.535 s 0.001 F001 0
" 67ED PUTT 1P Number of Communication Bits 0 to 2 --- 1 F198 0 (1)
" 67EE PUTT 1P Rx1 0 to 4294967295 --- 1 F300 0
" 67F0 PUTT 1P Rx2 0 to 4294967295 --- 1 F300 0
" 67F2 PUTT 1P Rx3 0 to 4294967295 --- 1 F300 0
" 67F4 PUTT 1P Rx4 0 to 4294967295 --- 1 F300 0
" 67F6 PUTT 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
" 67F7 PUTT 1P Event 0 to 1 --- 1 F102 0 (Disabled)
" 67F8 PUTT 1P Scheme Block 0 to 4294967295 --- 1 F300 0
" 67FA Reserved (5 items) 0 to 1 --- 1 F001 0
Pilot Hybrid POTT (1P) (Read/Write Setting)
D60, L90 6820 Hybrid POTT 1P Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
Products Address Register name Range Units Step Format Default