EasyManua.ls Logo

GE b30 - Page 113

GE b30
526 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-93
2
" 679D Phase Selector Reset 0 to 4294967295 --- 1 F300 0
" 679F Reserved (4 items) 0 to 1 --- 1 F001 0
Bus Configuration (Read/Write Setting) (6 Modules)
B90 679E ...Repeated for Bus Zone 6
Open Pole Detect (1P) (Read/Write Setting)
C60, D60, L60,
L90
67B0 Open Pole Function 0 to 1 --- 1 F102 0 (Disabled)
" 67B1 Open Pole Block 0 to 4294967295 --- 1 F300 0
" 67B3 Open Pole Voltage Supervision 0 to 1 --- 1 F102 0 (Disabled)
" 67B4 Open Pole Current Pickup 0.02 to 30 pu 0.001 F001 50
" 67B5 Open Pole Target 0 to 2 --- 1 F109 0 (Self-reset)
" 67B6 Open Pole Events 0 to 1 --- 1 F102 0 (Disabled)
" 67B7 Open Pole Line XC0 300 to 9999.9 ohms 0.1 F003 99999
" 67B9 Open Pole Line XC1 300 to 9999.9 ohms 0.1 F003 99999
" 67BB Open Pole Remote Current Pickup 0.02 to 30 pu 0.001 F001 50
" 67BC Open Pole Detection 0 to 1 --- 1 F608 0 (I AND V
AND CBaux)
" 67BD Open Pole Mode 0 to 1 --- 1 F607 0
(Accelerated
)
" 67BE Reserved (3 items) 0 to 1 --- 1 F001 0
Pilot DUTT (1P) (Read/Write Setting)
D60, L90 67D0 DUTT Function 0 to 1 --- 1 F102 0 (Disabled)
" 67D1 DUTT Seal In Delay 0 to 65.535 s 0.001 F001 0
" 67D2 DUTT 1P Number of Communication Bits 0 to 2 --- 1 F198 0 (1)
" 67D3 DUTT RX1 0 to 4294967295 --- 1 F300 0
" 67D5 DUTT RX2 0 to 4294967295 --- 1 F300 0
" 67D7 DUTT RX3 0 to 4294967295 --- 1 F300 0
" 67D9 DUTT RX4 0 to 4294967295 --- 1 F300 0
" 67DB DUTT 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
" 67DC DUTT 1P Event 0 to 1 --- 1 F102 0 (Disabled)
" 67DD DUTT 1P Scheme Block 0 to 4294967295 --- 1 F300 0
" 67DF Reserved (6 items) 0 to 1 --- 1 F001 0
Pilot PUTT (1P) (Read/Write Setting)
D60, L90 67EA PUTT 1P Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
" 67EB PUTT 1P Rx Pickup Delay 0 to 65.535 s 0.001 F001 0
" 67EC PUTT 1P Seal In Delay 0 to 65.535 s 0.001 F001 0
" 67ED PUTT 1P Number of Communication Bits 0 to 2 --- 1 F198 0 (1)
" 67EE PUTT 1P Rx1 0 to 4294967295 --- 1 F300 0
" 67F0 PUTT 1P Rx2 0 to 4294967295 --- 1 F300 0
" 67F2 PUTT 1P Rx3 0 to 4294967295 --- 1 F300 0
" 67F4 PUTT 1P Rx4 0 to 4294967295 --- 1 F300 0
" 67F6 PUTT 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
" 67F7 PUTT 1P Event 0 to 1 --- 1 F102 0 (Disabled)
" 67F8 PUTT 1P Scheme Block 0 to 4294967295 --- 1 F300 0
" 67FA Reserved (5 items) 0 to 1 --- 1 F001 0
Pilot Hybrid POTT (1P) (Read/Write Setting)
D60, L90 6820 Hybrid POTT 1P Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
Products Address Register name Range Units Step Format Default

Table of Contents

Other manuals for GE b30