2-92 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
Reduced Voltage Starting (Read/Write Setting)
M60 6750 Reduced Voltage Start Function 0 to 1 --- 1 F102 0 (Disabled)
" 6751 Reduced Voltage Start Transition Mode 0 to 2 --- 1 F095 0 (Current
Only)
" 6752 Reduced Voltage Start FLA (full load
current)
25 to 300 % 1 F001 125
" 6753 Reduced Voltage Start Timer 1 to 600 s 0.1 F001 100
" 6754 Reduced Voltage Start Block 0 to 4294967295 --- 1 F300 0
" 6756 Reduced Voltage Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6757 Reduced Voltage Start Event 0 to 1 --- 1 F102 0 (Disabled)
" 6758 Reserved (5 items) 0 to 1 --- 1 F001 0
Trip Output (Read/Write Setting)
C60, D60, L60,
L90
6760 Trip Mode 0 to 2 --- 1 F195 0 (Disabled)
" 6761 Trip 3-Pole Input1 0 to 4294967295 --- 1 F300 0
" 6763 Trip 3-Pole Input2 0 to 4294967295 --- 1 F300 0
" 6765 Trip 3-Pole Input3 0 to 4294967295 --- 1 F300 0
" 6767 Trip 3-Pole Input4 0 to 4294967295 --- 1 F300 0
" 6769 Trip 3-Pole Input5 0 to 4294967295 --- 1 F300 0
" 676B Trip 3-Pole Input6 0 to 4294967295 --- 1 F300 0
" 676D Trip 1-Pole Input1 0 to 4294967295 --- 1 F300 0
" 676F Trip 1-Pole Input2 0 to 4294967295 --- 1 F300 0
" 6771 Trip 1-Pole Input3 0 to 4294967295 --- 1 F300 0
" 6773 Trip 1-Pole Input4 0 to 4294967295 --- 1 F300 0
" 6775 Trip 1-Pole Input5 0 to 4294967295 --- 1 F300 0
" 6777 Trip 1-Pole Input6 0 to 4294967295 --- 1 F300 0
" 6779 Trip Reclose Input1 0 to 4294967295 --- 1 F300 0
" 677B Trip Reclose Input2 0 to 4294967295 --- 1 F300 0
" 677D Trip Reclose Input3 0 to 4294967295 --- 1 F300 0
" 677F Trip Reclose Input4 0 to 4294967295 --- 1 F300 0
" 6781 Trip Reclose Input5 0 to 4294967295 --- 1 F300 0
" 6783 Trip Reclose Input6 0 to 4294967295 --- 1 F300 0
" 6785 Trip Force 3-Pole 0 to 4294967295 --- 1 F300 0
" 6787 Trip Pilot Priority 0 to 65.535 s 0.001 F001 0
" 6788 Breaker Phase A Open 0 to 4294967295 --- 1 F300 0
" 678A Breaker Phase B Open 0 to 4294967295 --- 1 F300 0
" 678C Breaker Phase C Open 0 to 4294967295 --- 1 F300 0
" 678E Trip Events 0 to 1 --- 1 F102 0 (Disabled)
" 678F Reverse Fault Operand 0 to 4294967295 --- 1 F300 0
" 6791 Trip Delay On Evolving Faults 0 to 65.535 s 0.001 F001 0
" 6792 Trip Seal-In Delay 0 to 65.535 s 0.001 F001 0
" 6793 Trip Reset 0 to 2 --- 1 F609 0 (Pole Curr
OR Custom)
" 6794 Start Timer Zone 2 Phase Input 1 0 to 4294967295 --- 1 F300 0
" 6796 Start Timer Zone 2 Phase Input 2 0 to 4294967295 --- 1 F300 0
" 6798 Start Timer Zone 2 Ground Input 1 0 to 4294967295 --- 1 F300 0
" 679A Start Timer Zone 2 Ground Input 2 0 to 4294967295 --- 1 F300 0
" 679C Phase Selector Reset Delay 0.5 to 3 s 0.001 F001 500
Products Address Register name Range Units Step Format Default