CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-99
2
" 6C68 ...Repeated for RTD Input 39
" 6C7C ...Repeated for RTD Input 40
" 6C90 ...Repeated for RTD Input 41
" 6CA4 ...Repeated for RTD Input 42
" 6CB8 ...Repeated for RTD Input 43
" 6CCC ...Repeated for RTD Input 44
" 6CE0 ...Repeated for RTD Input 45
" 6CF5 ...Repeated for RTD Input 46
" 6D08 ...Repeated for RTD Input 47
" 6D1C ...Repeated for RTD Input 48
Undervoltage (Read/Write Grouped Setting) (12 Modules)
B90 6AF0 Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 6AF1 Undervoltage 1 VT 0 to 11 --- 1 F400 0
" 6AF2 Undervoltage 1 Pickup 0.004 to 3 pu 0.001 F001 800
" 6AF3 Undervoltage 1 Minimum Voltage 0 to 1 pu 0.001 F001 0
" 6AF4 Undervoltage 1 Pickup Delay 0 to 65.535 s 0.001 F001 0
" 6AF5 Undervoltage 1 Reset Delay 0 to 65.535 s 0.001 F001 0
" 6AF6 Undervoltage 1 Block 0 to 4294967295 --- 1 F300 0
" 6AF8 Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6AF9 Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 6AFA Undervoltage 1 Reserved (2 items) --- --- --- F001 0
" 6AFC ...Repeated for Undervoltage 2
" 6B08 ...Repeated for Undervoltage 3
" 6B14 ...Repeated for Undervoltage 4
" 6B20 ...Repeated for Undervoltage 5
" 6B2C ...Repeated for Undervoltage 6
" 6B38 ...Repeated for Undervoltage 7
" 6B44 ...Repeated for Undervoltage 8
" 6B50 ...Repeated for Undervoltage 9
" 6B5C ...Repeated for Undervoltage 10
" 6B68 ...Repeated for Undervoltage 11
" 6B74 ...Repeated for Undervoltage 12
End of Fault Protection / End Fault Protection (Read/Write Grouped Setting) (24 Modules)
B90 6B80 End of Fault Protection 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 6B81 End of Fault Protection 1 CT 0 to 23 --- 1 F400 0
" 6B82 End of Fault Protection 1 Pickup 0.02 to 30 pu 0.001 F001 1200
" 6B83 End of Fault Protection 1 Breaker Open 0 to 4294967295 --- 1 F300 0
" 6B85 End of Fault Protection 1 Breaker Delay 0 to 65.535 s 0.001 F001 400
" 6B86 End of Fault Protection 1 Manual Close 0 to 4294967295 --- 1 F300 0
" 6B88 End of Fault Protection 1 Pickup Delay 0 to 65.535 s 0.001 F001 40
" 6B89 End of Fault Protection 1 Block 0 to 4294967295 --- 1 F300 0
" 6B8B End of Fault Protection 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6B8C End of Fault Protection 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 6B8D ...Repeated for End of Fault Protection 2
" 6B9A ...Repeated for End of Fault Protection 3
" 6BA7 ...Repeated for End of Fault Protection 4
" 6BB4 ...Repeated for End of Fault Protection 5
Products Address Register name Range Units Step Format Default