EasyManua.ls Logo

GE b30 - Page 118

GE b30
526 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-98 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" 6979 RTD Input 1 Alarm Temperature 1 to 249 °C 1 F001 130
" 697A RTD Input 1 Alarm Pickup Delay 0 to 600 s 0.01 F001 0
" 697B RTD Input 1 Trip Temperature 1 to 249 °C 1 F001 130
" 697C RTD Input 1 Trip Pickup Delay 0 to 600 s 0.01 F001 0
" 697D RTD Input 1 Trip Reset Delay 0 to 600 s 0.01 F001 0
" 697E RTD Input 1 Trip Voting 0 to 48 --- 1 F551 0
" 697F RTD Input 1 Open 0 to 2 --- 1 F552 0 (None)
" 6980 RTD Input 1 Block 0 to 4294967295 --- 1 F300 0
" 6982 RTD Input 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6983 RTD Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 6984 ...Repeated for RTD Input 2
" 6998 ...Repeated for RTD Input 3
" 69AC ...Repeated for RTD Input 4
" 69C0 ...Repeated for RTD Input 5
" 69D4 ...Repeated for RTD Input 6
" 69E8 ...Repeated for RTD Input 7
" 69FC ...Repeated for RTD Input 8
" 6A10 ...Repeated for RTD Input 9
" 6A24 ...Repeated for RTD Input 10
" 6A38 ...Repeated for RTD Input 11
" 6A4C ...Repeated for RTD Input 12
" 6A60 ...Repeated for RTD Input 13
" 6A74 ...Repeated for RTD Input 14
" 6A88 ...Repeated for RTD Input 15
" 6A9C ...Repeated for RTD Input 16
" 6AB0 ...Repeated for RTD Input 17
" 6AC4 ...Repeated for RTD Input 18
" 6AD8 ...Repeated for RTD Input 19
" 6AEC ...Repeated for RTD Input 20
" 6B00 ...Repeated for RTD Input 21
" 6B14 ...Repeated for RTD Input 22
" 6B28 ...Repeated for RTD Input 23
" 6B3C ...Repeated for RTD Input 24
" 6B50 ...Repeated for RTD Input 25
" 6B64 ...Repeated for RTD Input 26
" 6B78 ...Repeated for RTD Input 27
" 6B8C ...Repeated for RTD Input 28
" 6BA0 ...Repeated for RTD Input 29
" 6BB4 ...Repeated for RTD Input 30
" 6BC8 ...Repeated for RTD Input 31
" 6BDC ...Repeated for RTD Input 32
" 6BF0 ...Repeated for RTD Input 33
" 6C04 ...Repeated for RTD Input 34
" 6C18 ...Repeated for RTD Input 35
" 6C2C ...Repeated for RTD Input 36
" 6C47 ...Repeated for RTD Input 37
" 6C54 ...Repeated for RTD Input 38
Products Address Register name Range Units Step Format Default